Faults – Atmos Energy INTERCOMBI HE32 User Manual

Page 44

Advertising
background image


44

8.

FAULTS

When the controller detects a fault, the red fault LED flashes (above the
Reset button) and a fault code is shown on the Temperature display.
After the fault has been remedied, the controller can be restarted by

pressing the Reset button for 5 secs.

The following faults are detected and displayed:-
Temperature
display

Description Possible

cause/remedy

10, 11, 12, 13, 14 Sensor fault S1

Check the wires for breaks

Replace S1

20, 21, 22, 23, 24 Sensor fault S2

Check the wires for breaks

Replace S2

0

Sensor fault after self-check

Replace boiler sensor S1 and/or S2

1

Temperature too high

Air in system

Pump does not run

Too little circulation in system, radiators closed,
pump setting too low

Flow switch stuck

2

Exchange S1 and S2

Check the cable loom

Replace S1 or S2

4

No flame signal

Gas tap closed

Incorrect ignition distance

Gas inlet pressure too low or disappears

Gas valve or ignition unit does not receive voltage

5

No flame signal

Condensate discharge blocked

Check setting of gas valve

6 Flame

detection

fault

Replace ignition cable + spark probe

Replace ignition unit

Replace controller

8

Fan speed incorrect

Fan rubs against casing

Wiring between fan and casing

Check the wires for poor contact (tacho signal)

Replace fan

29, 30

Gas valve relay fault

Replace controller