Burner resonates, No heating (ch) – Atmos Energy INTERCOMBI HE32 User Manual

Page 46

Advertising
background image


46

8.3

Burner resonates

Possible causes

8.4

No heating (CH)

1. Check the wiring.

2. Replace the thermostat.

3. Replace the weather-dependent control.

Room thermostat/weather-dependent

control not closed or faulty.

1. Check the voltage.

2. Check the connector x4.

3. Replace defective pump.

4. Replace defective controller.

1. Replace sensor S1 or S2.

See Fault code display: 1 or 2.

1. See Burner does not ignite.

Burner does not ignite.

Yes

No

Burner does not operate on CH: -

Sensor S1 or S2 faulty.

Yes

Pump does not run.

Yes

No

Yes

1. Check the wiring according to the

diagram.

2. Check the connector x4.

3. Replace defective controller

No voltage (24 V).

Yes

No

No

Possible causes

Remedies

1. The house gas meter may be faulty.

Inlet pressure too low.

Yes

Contact the gas company.

No

1. Check the adjustment,

see Gas-air control.

Gas-air mixture not adjusted properly.

Yes

1. Check the flue gases and air supply.

Re-circulation of the flue gases.

Yes

No

Remedies