3. Breeching

See Table 2 for minimum recommended breeching and chimney sizes.

Keep run boiler to chimney as short as possible.

Use as few elbows as possible.

Slope upward towards chimney at not less than 1/4” per foot.

Use a sealed-in thimble for the chimney connection.

Connect together all sections and/or fittings with sheet metal screws and
seal with silicone sealant.

4. When more than one appliance is connected to the same chimney, the chimney’s

internal cross-sectional area must be at a minimum equal to the area of the largest
vent plus 50% of the area of each additional vent.

5. Clearances—vent pipe between boiler and chimney must be a minimum of 6”

from any combustible material.

MINIMUM RECOMMENDED BREACHING AND CHIMNEY SIZE.

Boiler Model

Min. Breeching

Dia.

Min. Recommended
Chimney Size
I.D. HT.

OWB-9

6”

6” 15’

OWB-15

7”

7” 15’

OWB-25

7”

8” 20’

OWB-35

10”

10” 15’

OWB-50

10”

10” 15’


Table 2.

6. An oil-fired unit shall be connected to a flue having sufficient draft at all times, to

assure safe proper operation of the unit.