Indirect Water Heater

Supply to System

S

R

Circulating Pumps

Cold Water Feed

Shutoff Valve

Zone Valves

Return from System

Drain Cock

Figure 23.

7.

INTEGRATED SYSTEM, SINGLE OR MULTIPLE HEATING ZONES,
USING CIRCULATING PUMPS RATHER THAN ZONE VALVES----
Each pump will require a separate relay (Honeywell R845A or White Rodgers 828A-
845, or equivalent). Install a flow control valve in each zone including the indirect
water heater to prevent gravity circulation. Install a balancing valve in each zone and
adjust so that flow in each zone is about the same. (see Figure 24.) While this basic
system does not provide priority for domestic hot water, priority can be provided as
shown in Wiring Section, Figure 27.

Indirect Water Heater

Supply to System

Flow Control Valves

Shutoff Valve

S

Return from System

R

Cold Water Feed

Circulating Pumps

Drain Cock

Figure 24.

Installation, Operation, And Service Instructions