8.

COMBINATION HEATING/COOLING SYSTEM WITH CHILLED WATER
The chiller must be piped in parallel with the boiler and isolation valves installed to
prevent the chilled water from circulating through the boiler and heated water from
circulating through the chiller. See Figure 25.



S

Insulation
Valve # 4

Chiller

Circulating Pumps

Flow Check

Return from System

Insulation Valve # 3

Insulation Valve # 4

Supply to System

R

Cold Water Feed

Drain Cock

Note:
1.

When in cooling mode isolation valves 1 and 2 must be closed and valves 3 and 4 open.

2.

When in heating mode isolation valves 1 and 2 must be open and valves 3 and 4 closed.

Figure 25.

9.

SINGLE BOILER PIPING WITH BLEND PUMP

When burner is operating the water flow throughout the boiler shall be not less than
1.8 GPM for each 100,000 BTU/HR of gross boiler output. Size blend pump
accordingly. See Table 3


Blend Pump

Primary/Secondary

Pump

Boiler Model

GPM

GPM

OWB-9

OWB-15

OWB-25

OWB-35 16.3

78.9

OWB-50 19.6

94.9

Maximum water flow resistance for boilers is 14” w.c

Table 3.

30

Installation, Operation, And Service Instructions