2.6 Accuracy of the safe measuring function

The following information on the Total Safety Accuracy contains the following components:

Basic accuracy (measuring deviation from input and output, and the linearity error

of the transmitter)

In addition, for thermocouples, the internal cold-junction compensation (CJC),

except for type B thermocouples

Influence of the ambient temperature in the range -50 ... +85 °C

The defined value for the Total Safety Accuracy for this instrument depends on the

chosen sensor type, and the configured measuring span (see following table).

Up to the minimum spans given in the table, the Total Safety Accuracy is 2 % of the

measuring range with respect to the current output signal of 16 mA.

Otherwise, the absolute values given directly in the table are valid.

CAUTION!

The measuring span is the difference between the full scale value and the

initial value of a measuring range.

Sensor

type

Permissible

sensor range

for the accuracy

specifications

Min. span for

2 % total safety

accuracy

Absolute total

safety accuracy for

small measuring

spans

Pt100

-200 ... +850 °C

84 K

2 K

JPt100

-200 ... +500 °C

50 K

Ni100

-60 ... +250 °C

21 K

Pt1000

-200 ... +850 °C

69 K

2 K

Pt500

70 K

2 K

Pt25

134 K

3 K

Pt10

241 K

5 K

TC type T

-150 ... +400 °C

134 K

3 K

TC typeL

-150 ... +900 °C

138 K

TC type U -150 ... +600 °C

136 K

TC type E

-150 ... +1000 °C

164 K

4 K

TC type J

-150 ... +1200 °C

176 K

TC type K

-140 ... +1200 °C

197 K

TC type N -150 ... +1300 °C

154 K

TC type R +50 … +1600 °C

255 K

6 K

TC type S

+50 … +1600 °C

273 K

TC type B

+500 …+1820 °C

283 K