WIKA safety manual temperature transmitter T32.xS

11583631.02 11/2010 GB/D/F/E

2.4 Error signaling

The model T32.xS temperature transmitter monitors the connected sensors and its

own hardware for errors. In the event of a known error condition the device generates

an error signalling current.

The response time from the sensor is a maximum of 90 seconds.

This implies the discovery of the following potential errors:

Sensor burnout

Sensor short circuit (only for resistance temperature sensors, not for thermocouples)

Inadmissably high lead resistance (not with duplex resistance temperature sensors)

The online diagnosis-test interval of the instrument should be a maximum of

35 minutes. This implies the discovery of the following potential device errors:

ROM error

EEPROM error

RAM error

Program-counter error

Stack-pointer error

Furthermore, the following monitoring functions are carried out continuously:

Logical program flow control

Internal communications error

Over sensor upper limit

Under sensor lower limit

Cold junction temperature outside permissible limits (only for thermocouples)

Duplex sensor drift monitoring (activated optionally)

Configuration error

Monitoring of the permissible device temperature (optional, activated by default for

SIL versions)

Monitoring of the output limits (optional, not activated by default for SIL versions

starting from 01.01.2011)

CAUTION!

The device's error signalling current (error current) is configured in

accordance with the following requirements:

Error current fail high (high alarm value):

settable in the range ≥ 21.0 mA to ≤ 23.0 mA (upscale)

Error current fail low (low alarm value) :

settable in the range ≥ 3.5 mA to ≤ 3.6 mA (downscale)