WIKA safety manual temperature transmitter T32.xS

11583631.02 11/2010 GB/D/F/E

WARNING!

After the proof test of the device, start a functional check of the entire

safety function (safety loop) in order to test whether the transmitter

ensures the safety function of the system. Function tests are intended

to demonstrate the correct function of the whole safety-related system,

including all instruments (sensor, logic unit, and actuator).

2.9 Information on the determination of safety-relevant parameters

The failure rates of the electronics were determined using FMEDA in accordance

with IEC 61508. The calculations were based upon the component failure rates in

accordance with SN 29500.

The following assumptions have been made:

The transmitter are only operated in low demand mode applications.

The mean ambient temperature during the period of operation is 40 °C.

The MTTF following a device failure is 8 hours.

In accordance with ISO 13849-1 a maximum service life for the transmitter of 20 years

is assumed. Replace the device after this time.

2.10 Decommissioning the transmitter

WARNING!

Ensure dvices that have been taken out of service are not accidentally

recommissioned (e.g. through marking the instrument). After

decommissioning the temperature transmitter, a functional test of the

entire safety function (safety loop) should be initiated, in order to test

whether the safety function of the system is still ensured. Function tests

are intended to demonstrate the correct function of the whole safety-

related system, including all instruments (sensor, logic unit, and actuator).

2. Safety