WIKA safety manual temperature transmitter T32.xS

3.5 FMEDA

thermocouple with external cold junction

(safety function for 4 … 20 mA output)

λ

du

664 FIT

1)

λ

dd

6407 FIT

1)

λ

su

sd

118 FIT

1)

SFF – Safe Failure Fraction

90.7 %

MTTR

8 h

PFD for T

proof

1 year

2.91 * 10

-3

DC proof-test-coverage

incl. signal conditioning chain

99 %

3.6 FMEDA duplex sensor Pt100 (safety function for 4 … 20 mA output)

λ

du

57 FIT

1)

λ

dd

4017 FIT

1)

λ

su

sd

119 FIT

1)

SFF – Safe Failure Fraction

98.8 %

MTTR

8 h

PFD for T

proof

1 year

2.495 * 10

-4

DC proof-test-coverage

incl. signal conditioning chain

99 %

3.7 FMEDA duplex sensor thermocouple with internal cold junction

(safety function for 4 … 20 mA output)

λ

du

516 FIT

1)

λ

dd

9557 FIT

1)

λ

su

sd

117 FIT

1)

SFF – Safe Failure Fraction

95.3 %

MTTR

8 h

PFD for T

proof

1 year

2.262 * 10

-3

DC proof-test-coverage

incl. signal conditioning chain

99 %

1) FIT = Failure in time, Unit: Quantity of failures per 10

9

h

Appendix 1: SIL Declaration of Conformity

SIL Declaration of Conformity

Functional safety per DIN EN 61508 / DIN EN 61511

Page 3/3