Medium Power Substation Transformers

Document 2.4.06, Revision 4

June 2013

17

Winding temperature gauges can be supplied with an

alarm/signal switch. Refer to the schematic wiring

diagram furnished with the transformer.

Thermal Overload Relay

Transformers may be supplied with a thermal overload

relay, which is similar in operation to the winding

temperature gauge described above. The relay provides

alarm/signal contacts that close at approximately 100%

and 110% rated load.

Rapid Pressure Rise Relay

The optional Rapid Pressure Rise Relay (RPRR) monitors

the rate of pressure rise in the transformer’s gas space

and signals when the rate exceeds a safe threshold.

This signal can trigger circuit breaker operation to de-

energize the transformer and can send an alarm. The

RPRR will not be actuated by normal pressure variations

during operation of the transformer. A seal-in relay

latches the output relay and illuminates an indicator

lamp until the unit is manually reset. The seal-in relay

and associated circuitry is mounted in a separate control

cabinet.

If the RPRR has activated, internal arcing has likely

occurred in the transformer tank, and the cause of such

arcing must be investigated. The following steps are

suggested to determine the extent of damage to the

transformer, in any.

1. Using a combustible gas detector, check for

combustible gas products of decomposition

in the gas space. Refer to the operating

instructions that came with the gas detector.

2. Test the RPRR and seal-in relay panel to make

sure they are operating properly. Refer to

instructions furnished with RPRR and seal-in

relay panel.

3. Test for insulation power factor, insulation

resistance tests, and transformer turns ratio.

4. Remove the manhole cover and inspect the tank

interior for appearance and smell. (A burning

odor may be present.)

5. Make any other tests which may be appropriate

considering results of the tests listed above.

WARNINg

: DO NOT ATTEMPT TO

DISASSEMBlE A PRESSURE RElIEF DEvICE.

TO DO SO COUlD RESUlT IN EQUIPMENT DAMAGE

AND SEvERE PERSONAl INJURY.

PRD’s can be supplied with an optional alarm/signal

switch. Refer to the schematic wiring diagram furnished

with the transformer.

Fluid level gauge

The fluid level gauge indicates the fluid level inside the

tank. The transformer tank is filled with fluid at the

factory to the normal level at a reference temperature of

25°C.

Fluid Temperature gauge

The fluid temperature gauge indicates the fluid

temperature at the top of the fluid column. The

temperature gauge is mounted in a dry, leak proof

well, permitting removal of the gauge without lowering

the fluid level in the tank. The gauge is furnished with

a resettable drag-hand pointer which indicates the

maximum temperature reached since it was last reset.

The drag-hand can be reset by rotating the magnet at

the center of the dial or, on some models, by pressing a

reset button.

During normal operation the fluid temperature

gauge should read less than the sum of the ambient

temperature and the rated temperature rise. For

example, a 50°C gauge reading at an ambient

temperature of 25°C yields a top oil temperature of

75°C, which is below the transformer’s 85°C rated

temperature rise.

Winding Temperature gauge

Transformers may be furnished with a gauge that

displays estimated winding hot-spot temperature. The

gauge uses a probe that measures the temperature of

the transformer fluid plus auxiliary heat from a heating

element that is energized by a current transformer

mounted inside the transformer tank.

The gauge’s temperature probe is mounted in a dry well,

permitting removal of the gauge without lowering the

fluid level. The gauge is furnished with a resettable drag-

hand pointer that indicates the maximum temperature

reached since it was last reset. The drag-hand can be

reset by rotating the magnet at the center of the dial, or

on some models, by means of a pushbutton.