Howard Medium Power Substation User Manual

Page 18

Advertising
background image

Document 2.4.06, Revision 4

June 2013

Medium Power Substation Transformers

18

Transformer Cooling Fans

Optional cooling fans may be provided to increase

the transformer load capability without overheating

the transformer windings. Operation of the fans is

controlled by a contact in the fluid temperature gauge

or winding temperature gauge (when furnished) and

by an “auto/manual” control switch. Controls for the

fans are contained in a control cabinet mounted on the

transformer.

DANgER

: AlWAYS DE-ENERGIZE THE FAN

CIRCUIT WHEN INSTAllING OR PERFORMING

MAINTENANCE ON FANS. IN ADDITION, DE-ENERGIZE

THE TRANSFORMER WHEN IT IS POSSIBlE TO COME

ClOSE TO ElECTRICAllY CHARGED/lIvE PARTS.

FAIlURE TO DO SO COUlD RESUlT IN SEvERE

PERSONAl INJURY OR DEATH. FAN GUARDS ARE

FURNISHED AND INSTAllED AT THE FACTORY TO

PREvENT ACCIDENTAl CONTACT WITH ROTATING FAN

BlADES. DO NOT REMOvE FAN GUARDS OR AllOW

PERSONNEl TO REACH INSIDE A GUARD. DOING SO

CAN RESUlT IN SERIOUS PERSONAl INJURY AND

EQUIPMENT DAMAGE.

The auto/manual switch determines the mode of

operation for the fan motors. When the switch is in

the “manual” position, fans will operate continuously.

When the switch is in the “auto” position, fans will

be automatically controlled by contacts in the fluid

temperature gauge or winding temperature gauge.

Refer to the schematic wiring diagram provided with the

transformer.

Fan motors are provided with thermal overload

protection. The overload protection is usually contained

within the motor. However, if the motors are located in a

hazardous location, the overload protection device may

be located in the control box. Refer to the wiring diagram

provided with the transformer.

Fan motors have permanently sealed ball bearings

and do not normally require maintenance, except as

explained on Page 20.

When fan assemblies are installed by the user, it

is important to permanently remove the drain plug

from the motor housing of each motor. This will allow

condensation to drain from the motor housing.

De-Energized Tap Changer

The de-energized tap changer may be used to adjust the

voltage ratio of a transformer while it is de-energized.

It is intended to allow adjustment of the output

(secondary) voltage to the rated value. Do not use the

tap changer to raise or lower the output voltage to any

voltage other than that indicated on the transformer

nameplate. If the tap changer is set to provide an output

voltage different from rated voltage, a high noise level,

high core loss, and core saturation may result.

DANgER

: DO NOT OPERATE A DE-ENERGIZED

TAP CHANGER UNlESS THE TRANSFORMER IS

TOTAllY DE-ENERGIZED. FAIlURE TO DO SO WIll

RESUlT IN DAMAGE TO THE TRANSFORMER AND

COUlD RESUlT IN SEvERE PERSONAl INJURY OR

DEATH. DO NOT RE-ENERGIZE THE TRANSFORMER

UNlESS THE TAP CHANGER IS FIRMlY lOCKED INTO

POSITION.

The tap changer is operated by use of a rotating

handle located on the outside of the transformer tank.

Never operate a de-energized tap changer while the

transformer is energized. Tap changers normally have

five or seven tap positions as indicated on the tap

changer dial plate and the transformer nameplate. A

locking mechanism is provided to lock the tap changer

in position and prevent accidental operation. Do not

re-energize the transformer until the tap changer is firmly

locked into a tap position.

The transformer is shipped from the factory with the tap

changer in the rated voltage position, unless otherwise

specified by the customer.

Dual-voltage or Delta/Wye Switch

Transformers designed with dual-voltage windings or

reconnectable delta/wye windings as indicated on the

nameplate are provided with a de-energized two-position

dual-voltage or delta/wye switch. The transformer must

be completely de-energized before operating the switch.

If the transformer is not de-energized before operating

the switch, permanent damage will result.

WARNINg

: DO NOT OPERATE DUAl-vOlTAGE OR

DElTA/WYE SWITCH UNlESS THE

TRANSFORMER IS TOTAllY DE-ENERGIZED.

FAIlURE TO DO SO WIll RESUlT IN DAMAGE TO THE

TRANSFORMER AND COUlD RESUlT IN SEvERE

PERSONAl INJURY OR DEATH. DO NOT RE-ENERGIZE

THE TRANSFORMER UNlESS THE DUAl-vOlTAGE

OR DElTA/WYE SWITCH IS FIRMlY lOCKED INTO

POSITION.

Advertising