4 options, 5 accessories, Options – ADC PowerWorx Power Distribution Products User Manual

Page 10: Accessories

Advertising
background image

ADCP-80-545 • Issue 3 • March 2006

Page 4
© 2006, ADC Telecommunications, Inc.

• One set of 23-inch mounting brackets

• 5/16-inch long, Phillips drive, 8-32 flat-head thread-forming screws (10 provided which

includes 2 spares) - Used to secure the mounting brackets to the panel.

• 3/8-inch long, combination drive, 12-24 pan-head screws (4) and #12 flat washers (4) -

Used to secure the panel mounting brackets to the equipment rack.

• 2-hole lugs (4) for #2 AWG wire - Used to attach the BATTERY and RETURN cables to

the power input terminals. Also available as an accessory item.

• #10 ring terminals (2) for 12–10 AWG wire - Used to connect the grounding cables to the

grounding studs.

• Rear protective input terminal covers (2) and output terminal covers (4) - Used to prevent

accidental contact with the power input and output terminals.

• Voltage label - Used to indicate the voltage of the panel (–24 or –48 Vdc).

• Designation cards (2) and card holder - Used to record information about the protected

equipment. The card holder has a pressure sensitive adhesive backing to permit attachment
to the panel, the rack, or a location close to the panel. The card inserts into the card holder.
Two types of cards are provided. Also available as an accessory item.

1.4

Options

The following ordering options are available for the Select Series circuit breaker panel:

• Circuit breaker configurations - Circuit breakers may be specified in any combination of

values as long as the total current draw on each bus does not exceed 100 Amps. A
maximum of eight 1-pole breakers or four 2-pole breaker may be installed per bus.

• Circuit breaker ratings - Both 1-pole and 2-pole circuit breakers are used with the panel.

The 1-pole breakers are available with 1, 3, 5, 10, 15, or 20 Amp ratings. The 2-pole
breakers are available with 26, 30, 36, 40, and 50 Amp ratings.

• Alarm contact connections - Either screw-down terminals or wire-wrap pin terminals may

be specified for the alarm contact connections.

1.5

Accessories

The following accessories are available for the Select Series circuit breaker panel:

• Circuit breakers - 1-pole breakers with a rating of 1, 3, 5, 10, 15, and 20 Amps and 2-pole

breakers with a rating of 26, 30, 36, 40, and 50 Amps are available.

• 2-hole compression lugs - Used to attach the BATT and RTN cables to the power input

terminals. Available to fit 2, 4, 6, or 14 AWG wire.

• Cable management bar - Use to secure the output power wires at the rear of the panel.

• Designation cards (2) and card holder - Used to record information about the protected

equipment. The card holder has a pressure sensitive adhesive backing to permit attachment

Advertising