ADCP-80-545 • Issue 3 • March 2006

Page 27

Figure 19. Single-Pole Circuit Breaker Wiring Connections

Figure 20. Two-Pole Circuit Breaker Wiring Connections

10. Connect the two alarm wires to the specified terminals on the rear side of the replacement

circuit breaker (see

Figure 19

or

Figure 20

).

11. Insert the replacement circuit breaker into the opening in the panel and push inward until it

locks into place.

12. Reconnect the power to the power bus.

Note: Do not connect any wires to the center terminal on the circuit breaker.

LINE

POWER

(WHITE)

LOAD

(BLACK)

BREAKER ALARM

CONNECTIONS

LOCKING

TAB

LOCKING

TAB

17339-C

NOT USED

FRONT VIEW

SIDE VIEW

LINE

POWER

(WHITE)

LOAD

(BLACK)

LOAD

(BLACK)

LOAD

(BLACK)

BREAKER ALARM

CONNECTIONS

BREAKER ALARM

CONNECTIONS

LOCKING

TAB

LOCKING

TAB

NOT USED

SIDE VIEW

TOP VIEW

18146-C

FRONT VIEW