9 circuit designation card and voltage label, Cable management bar installation (accessory item), Circuit designation card and voltage label – ADC PowerWorx Power Distribution Products User Manual

Page 27

Advertising
background image

ADCP-80-545 • Issue 3 • March 2006

Page 21

© 2006, ADC Telecommunications, Inc.

To provide access to the input and output power terminals, it may sometimes be necessary to
remove the protective rear covers. To remove a cover, pull outward on the cover until it comes
free of the terminal block.

3.8

Cable Management Bar Installation (Accessory Item)

The cable management bar is an accessory item that may be attached to the rear side of the
circuit breaker panel as shown in

Figure 15

. Align the cable management bar with the holes on

the sides of the chassis. The bar can be recess mounted by using the holes that are closest to the
front of the panel. Use the six 1/4-inch (6.35 mm) long 4-40 thread-forming screws provided to
secure the cable management bar to the sides of the circuit breaker panel chassis.

Figure 15. Cable Management Bar Installation

3.9

Circuit Designation Card and Voltage Label

A circuit designation card holder and card (2), shown in

Figure 16

, are provided with the circuit

breaker panel. Fill out one of the designation cards with the required circuit information and
insert it into the card holder. Attach the card holder to the circuit breaker panel or to any
convenient location that is close to the panel. The card holder has a pressure sensitive adhesive
back for attachment.

A voltage designation label (see

Figure 16

) is also provided with the circuit breaker panel. Enter

the voltage level (measured during testing) for the panel (–24 or –48 Vdc) in the spaces
provided. Attach the voltage label to any convenient mounting point on the panel. The voltage
label has a pressure sensitive adhesive back for attachment.

Caution: When attaching the cable management bar to the circuit breaker panel, use only the 1/
4-inch (6.35 mm) long, 4-40 thread-forming screws provided with the panel. Use of any other
hardware could cause contact with internal parts of the panel. If parts are missing, contact
ADC to order replacement parts.

17935-A

CABLE

MANAGEMENT

BAR

ATTACH TO

EITHER SET
OF 3 HOLES

MOUNTING BRACKET

INSTALLED FOR

23-IN. (58.42 CM)

RACK MOUNTING