22

2. Technical Gas Data

a. Gas Specifications

b. Gas Connections:

Inlet connection --- 1/2-inch N.P.T.
Inlet supply size --- 1/2-inch N.P.T. (minimum)
Btu/hr input -------- 78,000 (19,657 kcal/hr)

1) Natural Gas

Regulation is controlled by the dryer’s gas valve’s internal regulator. Incoming supply pressure
must be consistent between a minimum of 6.0 inches (14.92 mb) and a maximum of 12.0 inches
(29.9 mb) water column (W.C.) pressure.

2) Liquid Propane (L.P.) Gas

Dryers made for use with L.P. gas have the gas valve’s internal pressure regulator blocked open so
that the gas pressure must be regulated upstream of the dryer. The pressure measured at each gas
valve pressure tap must be a consistent 10.5 inches (26.1 mb) water column. There is no regulator
or regulation provided in a L.P. dryer. The water column pressure must be regulated at the source
(L.P. tank) or an external regulator must be added to each dryer.

*

Drill Material Size (D.M.S.) equivalents are as follows:

Natural Gas ................ #32 = 0.1160” (2.9464 mm).
Liquid Propane Gas ... #50 = 0.0700” (1.778 mm).

T

YPE OF

G

AS

Liquid Propane

(L.P.)

Conversion

Kit

Part Number

ADC

MODEL

NUMBER

BTU

Per Hour

Rating

kcal/hr

Rating

Natural

Liquid Propane (L.P.)

Qty.

D.M.S.*

Part

Number

Qty.

D.M.S.*

Part

Number

ADG-27D

78,000

19,657

2

#32

140851

2

#50

140802

881134

Shaded area is stated in metric equivalent

T

YPE OF

G

AS

Natural

Liquid Propane (L.P.)

Manifold Pressure*

3.5 inches W.C.

8.7 mb

10.5 inches W.C.

26.1 mb

Inline Pressure

6.0 - 12.0 inches W.C.

14.92 - 29.9 mb

10.5 inches W.C.

26.1 mb

Shaded areas are stated in metric equivalents

* Measured at outlet side of gas valve pressure tap when the gas valve is on.