Receiving & Installation 3-3

MN2403

Frame Ground Connection
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power

before you ensure that grounds are connected. Electrical shock can cause serious or fatal

injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be

connected to an approved earth ground. Local codes may also require proper grounding of

generator systems.

The NEC requires that the frame and exposed metal surfaces be at local ground reference

potential to avoid electrical shock hazard. A local ground reference may require a driven earth

ground conductor at the generator installation site. Make the ground connection as shown in

Figure 3-2. Use the appropriate size wire (normally 6 AWG) as required by NEC and local

codes. The local reference ground is normally a copper clad earth ground rod driven into the

earth at least 8 feet.

Figure 3-2 Frame Ground Connection

Engine Oil

The generator is shipped dry. This means no oil is in the engine crankcase and no fuel is in the

fuel tank. Refer to section 5 of this manual for lubricant and fuel requirements and obtain the

correct type and quantity of engine motor oil and fuel.

1.

Refer to section 5 of this manual and add the required amount of engine oil.

2.

Refer to section 5 of this manual and add the appropriate amount of fuel.

After installation, the post installation checks must be performed prior to starting the engine.

After these checks have been performed and the system operation is verified to be good, refer to

Section 5 Maintenance for periodic checks that must be performed at scheduled intervals to

ensure continued operation with minimal problems.