PERFORMANCE DATA (cont)

NET COOLING CAPACITIES (cont)

582A060

TEMP (F)

OUTDOOR-AIR

ENTERING

CONDENSER

EVAPORATOR AIR – CFM/BF

1750/0.039

Evaporator Air – Ewb (F)

62

67

72

62

67

72

62

67

72

85

TC

53.9

61.5

69.3

56.1

63.6

71.1

58.0

65.2

72.4

SHC

48.8

41.4

33.4

53.7

45.2

35.7

58.0

48.8

37.9

kW

6.12

6.33

6.52

6.21

6.38

6.57

6.25

6.42

6.62

95

TC

50.7

58.1

65.8

52.8

60.0

67.5

55.2

61.4

68.8

SHC

47.4

40.1

32.2

51.9

43.9

34.5

55.2

47.4

36.7

kW

6.44

6.69

6.89

6.53

6.74

6.94

6.63

6.78

6.98

105

TC

47.2

54.4

62.2

49.6

56.1

63.7

52.2

57.5

64.9

SHC

45.7

38.7

30.9

49.6

42.5

33.3

52.2

46.0

35.5

kW

6.75

7.07

7.27

6.87

7.11

7.33

7.01

7.15

7.37

115

TC

43.7

50.4

58.2

46.6

52.0

59.6

49.1

53.3

60.7

SHC

43.7

37.2

29.6

46.6

40.9

32.0

49.1

44.4

34.2

kW

7.08

7.43

7.67

7.24

7.50

7.73

7.38

7.53

7.77

LEGEND

Ewb –

Entering Wet-Bulb

kW

Total Unit Power Input

SHC –

Sensible Heat Capacity (1000 Btuh)

TC

Total Capacity (1000 Btuh) (net)

NOTES:
1. Ratings are net; they account for the effects of the evaporator-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:

sensible capacity (Btuh)

t

= t

؊

ldb

edb

1.10 x cfm

t

= Wet-bulb temperature corresponding to enthalpy of air leaving

lwb

evaporator coil (h

)

lwb

total capacity (Btuh)

h

= h

؊

lwb

ewb

4.5 x cfm

Where: h

= Enthalpy of air entering evaporator coil

ewb

13