Bryant 582A User Manual

Page 8

Advertising
background image

BASE UNIT DIMENSIONS – 582A048-060

FLUE HOOD

REQ'D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)

Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . . . . . . . . . 36 (914)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 36 (914)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*

*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall

system, then the system performance may be compromised.

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)

NEC REQ'D CLEARANCES. in. (mm)

Between units, power entry side

. . . . . . . . . . . . . . 42 (1066.8)

Unit and ungrounded surfaces, power entry side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side

. . . . . . . . . . . . . . . . . 42 (1066.8)

LEGEND

CG

Center of Gravity

COND

Condenser

EVAP

Evaporator

NEC

National Electrical Code

REQ'D –

Required

NOTE: Dimensions are in mm [in.]

UNIT
582A

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

CENTER OF GRAVITY

in. [mm]

lb

kg

X

Y

Z

048090/115/130

208-230/1/60, 208/230-3-60, 460-3-60

415

188.6

22 [558.5]

16 [406.4]

17 [432.0]

060090/115/130

208/230-1-60, 208/230-3-60, 460-3-60

450

204.5

22 [558.5]

16 [406.4]

17 [432.0]

8