GUIDE SPECIFICATIONS (cont)

K. Electrical Requirements:

All unit power wiring shall enter the unit cabinet at a
single location.

L. Motors:

1. Compressor motors shall be of the refrigerant-cooled

type with line-break thermal and current overload
protection.

2. All fan motors shall have permanently lubricated bear-

ings, and inherent, automatic reset, thermal overload
protection.

3. Condenser-fan motor shall be totally enclosed.

M. Special Features:

1. Louvered Grille:

Wire grille shall be standard on all units. Louvered
grille shall be available as a factory-installed option
to provide hail guard and vandalism protection.

2. Coil Options:

Shall include factory-installed optional copper/copper
and vinyl-coated refrigerant coils.

3. Economizer:

a. Economizer controls capable of providing free

cooling using outside air.

b. Equipped with low leakage dampers not to

exceed 3% leakage, at 1.0 in. wg pressure
differential.

c. Spring return motor shuts off outdoor damper on

power failure.

4. Flat Roof Curb:

Curbs shall have seal strip and a wood nailer for
flashing and shall be installed per manufacturer’s
instructions.

5. Manual Outdoor Air Damper:

Package shall consist of damper, birdscreen, and
rainhood which can be preset to admit outdoor air for
year-round ventilation.

6. Thermostat:

To provide for one-stage heating and cooling in ad-
dition manual or automatic changeover and indoor
fan control.

7. Natural-to-Propane Conversion Kit:

Shall be complete with all required hardware to con-
vert to liquid propane (LP) operation at 3.5 in. wg
manifold pressure.

8. Low Ambient Package:

Shall consist of a solid-state control and condenser
coil temperature sensor for controlling condenser-fan
motor operation, which shall allow unit to operate
down to 0

°

F outdoor ambient temperature.

9. Filter Rack Kit:

Shall provide filter mounting for downflow
applications.

10. Controls Upgrade Kit:

Shall

provide

high

and

low

pressure

safety

protection.

11. Square-To-Round Duct Transitions:

Shall have the ability to convert the supply and return
openings from rectangular to round.

12. Compressor Protection:

Solid-state control shall protect compressor by pre-
venting “short cycling.”

13. Duct Conversion Kit:

Shall enable conversion of a factory-supplied side
discharge unit to horizontal discharge airflow unit.

14. Crankcase Heater:

Shall provide anti-floodback protection for low-load
cooling applications.

15. High-Altitude Kit:

Shall consist of natural gas orifices to compensate
for gas heat operation at 2001 to 4500 ft above sea
level.

16. Low NO :

x

Shall provide NO

x

reduction to values below

40 nanograms/joule to meet California emission
requirements as shipped from the factory.

17. Compressor Hard Start Kit:

Shall provide additional starting torque for single-
phase compressors.

© 2000 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE

WITH INSTALLATION INSTRUCTIONS

Printed in U.S.A.

CATALOG NO. 5258-202