Physical data – Bryant 582A User Manual

Page 4

Advertising
background image

PHYSICAL DATA

UNIT SIZE 582A

018040

024040

024060

030040

030060

036060

036090

042060

042090

NOMINAL CAPACITY (ton)

1

1

/

2

2

2

2

1

/

2

2

1

/

2

3

3

3

1

/

2

3

1

/

2

OPERATING WEIGHT (lb)

249

280

280

280

280

314

314

355

355

COMPRESSOR(S) – QUANTITY

Reciprocating-1

REFRIGERANT

(R-22)

Quantity (lb)

2.6

3.5

3.5

3.65

3.65

3.75

3.75

5.7

5.7

REFRIGERANT METERING DEVICE

Acutrol™ Device

Orifice ID (in.)

.034

.034

.034

.034

.034

.032

.032

.034

.034

CONDENSER COIL

Rows—Fins/in.

1—17

1—17

1—17

1—17

1—17

1—17

1—17

1—17

1—17

Face Area (sq ft)

6.1

9.1

9.1

9.1

9.1

9.1

9.1

9.1

9.1

CONDENSER FAN

Nominal Cfm

2000

2400

2400

2400

2400

3000

3000

3000

3000

Diameter

22

22

22

22

22

22

22

22

22

Motor Hp (Rpm)

1

/

8

(825)

1

/

8

(825)

1

/

8

(825)

1

/

8

(825)

1

/

8

(825)

1

/

4

(1100)

1

/

4

(1100)

1

/

4

(1100)

1

/

4

(1100)

EVAPORATOR COIL

Rows—Fins/in.

2—15

2—15

2—15

2—15

2—15

3—15

3—15

4—15

4—15

Face Area (sq ft)

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

EVAPORATOR BLOWER

Nominal Airflow (Cfm)

600

800

800

1000

1000

1200

1200

1400

1400

Size (in.)

10 x 10

10 x 10

10 x 10

10 x 10

10 x 10

11 x 10

11 x 10

11 x 10

11 x 10

Motor (Hp)

1

/

4

1

/

4

1

/

4

1

/

4

1

/

4

1

/

2

1

/

2

3

/

4

3

/

4

FURNACE SECTION*

Burner Orifice No. (Qty—Drill Size)

Natural Gas

2—44

2—44

2—38

2—44

2—38

2—38

3—38

2—38

3—38

Burner Orifice No. (Qty—Drill Size)

Propane Gas

2—52

2—52

2—46

2—52

2—46

2—46

3—46

2—46

3—46

RETURN-AIR FILTERS (in.)†

Throwaway Size

20 x 20 x 1

20 x 20 x 1

20 x 20 x 1

20 x 20 x 1

20 x 20 x 1

20 x 24 x 1

20 x 24 x 1

20 x 24 x 1

20 x 24 x 1

UNIT SIZE 582A

048090

048115

048130

060090

060115

060130

NOMINAL CAPACITY (ton)

4

4

4

5

5

5

OPERATING WEIGHT (lb)

415

415

415

450

450

450

COMPRESSOR(S) – QUANTITY

Scroll-1

Reciprocating-1

REFRIGERANT

(R-22)

Quantity (lb)

6.0

6.0

6.0

8.0

8.0

8.0

REFRIGERANT METERING DEVICE

Acutrol Device

Orifice ID (in.)

.032

.032

.032

.030

.030

.030

CONDENSER COIL

Rows—Fins/in.

1—17

1—17

1—17

2—17

2—17

2—17

Face Area (sq ft)

12.3

12.3

12.3

12.3

12.3

12.3

CONDENSER FAN

Nominal Cfm

3600

3600

3600

3600

3600

3600

Diameter (in.)

22

22

22

22

22

22

Motor Hp (Rpm)

1

/

4

(1100)

1

/

4

(1100)

1

/

4

(1100)

1

/

4

(1100)

1

/

4

(1100)

1

/

4

(1100)

EVAPORATOR COIL

Rows—Fins/in.

3—15

3—15

3—15

4—15

4—15

4—15

Face Area (sq ft)

4.7

4.7

4.7

4.7

4.7

4.7

EVAPORATOR BLOWER

Nominal Airflow (Cfm)

1600

1600

1600

2000

2000

2000

Size (in.)

11 x 10

11 x 10

11 x 10

11 x 10

11 x 10

11 x 10

Motor (Hp)

3

/

4

3

/

4

3

/

4

1.0

1.0

1.0

FURNACE SECTION*

Burner Orifice No. (Qty—Drill Size)

Natural Gas

3—38

3—33

3—31

3—38

3—33

3—31

Burner Orifice No. (Qty—Drill Size)

Propane Gas

3—46

3—42

3—41

3—46

3—42

3—41

RETURN-AIR FILTERS (in.)†

Throwaway Size

24 x 30 x 1

24 x 30 x 1

24 x 30 x 1

24 x 30 x 1

24 x 30 x 1

24 x 30 x 1

*Based on altitude of 0 to 2000 feet.

†Required filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration

Institute) rated. The filter rack is field convertible to hold a field supplied 2 in. filter.

4

Advertising