Model 702GAS Advanced gas burners — Instruction manual

Carlin part number MN702G Rev. 03/14/11

– 13 –

Where appliance instructions differ from this manual, follow the appliance instructions.

Table 3

Capacities of black iron pipe, cubic feet gas/hour

NATURAL GAS

Capacities in Cubic feet per hour

for Schedule 40 metal pipe

Pipe

size

(inches)

Total length of gas piping,

from meter to burner connection (feet)

20

40

60

80

100

Natural gas @ .60 specific gravity, pressure drop 0.3 in. w.c.

(note 1)

730

500

400

350

305

1,100

760

610

530

460

2

2,100

1,450

1,150

990

870

3,300

2,300

1,850

1,600

1,400

Natural gas @ .60 specific gravity, pressure drop 0.5 in. w.c.

(note 1)

950

660

530

460

400

1,460

990

810

690

620

2

2,750

1,900

1,520

1,300

1,150

4,350

3,000

2,400

2,050

1,850

Note 1

For natural gas with specific gravity other than 0.60,

consult National Fuel Gas Code for correction factor.

PROPANE GAS

Capacities in Btuh for

Schedule 40 metal pipe

Pipe size

(inches)

Total length of gas piping,

from meter to burner connection (feet)

20

40

60

80

100

Propane gas @ 1.5 specific gravity, pressure drop 1 psi

½

1,839

1,264

1,015

869

770

¾

3,845

2,643

2,122

1,816

1,610

1

7,243

4.978

3,998

3,422

3,033

Propane gas @ 1.5 specific gravity, pressure drop 0.5 in. w.c.

1

787

541

434

372

330

1,616

1,111

892

677

543

2,422

1.664

1,337

1,114

1,014

Figure 8 Gas train pressure drop

3. Install gas piping

(continued)

Regulator spring:

The standard main gas pressure regulator spring (see
item 8, Figure 7, page 12) is plated. The range is from
3.0 to 6.0 inches water column.

The 1” RV61 regulator is available with an optional
blue spring, with a range of 5.0 to 12.0 inches water
column.

The 1¼” or 1½” RV81 regulator is available with the
standard plated spring (3.0 to 6.0 inches water column)
or a violet spring, with a range of 4.0 to 12.0 inches
water column.

PROPANE applications — A brown spring (1.0” to
3.5” w.c. range) may be required for propane.