Step 5, Adjust the burner using test instruments, Verify operation – Carlin 702GAS Inst Manual User Manual

Page 21

Advertising
background image

Model 702GAS Advanced gas burners — Instruction manual

Carlin part number MN702G Rev. 03/14/11

– 21 –

Where appliance instructions differ from this manual, follow the appliance instructions.

Step 5

Verify operation

Burner/appliance/controls operation

Test operating and limit controls on appliance as specified in appliance instructions.

Check operation of the primary control by forcing lockout to occur. For primary controls that enter latch-up after multiple lockouts, force latch-up
to occur as well. Reset primary control per control data sheet instructions after each test.

Start and stop the burner several times, allowing the primary control to sequence through normal operation. Verify correct operation of burner and
primary control.

Confirm and/or adjust overfire pressure reading in combustion chamber. Refer to boiler/furnace manufacturer’s recommendations.

Verify vent system operation

Verify vent is operating correctly and flue products are properly exhausted from building. If the building contains any exhaust fans or conditions that
could affect vent performance, check burner/appliance/vent operation with exhaust fans (or other conditions) operating.

Combustion/ventilation air

Verify combustion/ventilation air openings are not, and will not be obstructed.

Verify air opening louvers are fully open.

If louvers are motor-operated, verify motor and end switch are interlocked with appliance/burner wiring to prevent operation of the burner if the air
louvers are not fully opened.

Prepare burner for normal operation

Cycle burner off with appliance controls.

Turn off power to the appliance.

Seal the appliance flue test opening.

Verify all components and wires are in place and burner is ready for operation.

Restore power to the appliance.

Train the user

Train the user to operate the burner and appliance under normal conditions.

Explain the procedure to shut down the burner/appliance when required.

Review the back cover of this manual (and the appliance manual) with the user.

Verify the user is aware of all procedures specified in the manuals.

Verify that the user will not store or use combustible liquids or materials or contaminants in the vicinity of the burner/appliance.

7. Adjust the burner using test instruments