Checkout procedure — before starting the burner, Before firing the burner, Checklist before firing – Carlin 702GAS Inst Manual User Manual

Page 16

Advertising
background image

Model 702GAS Advanced gas burners — Instruction manual

Carlin part number MN702G Rev. 03/14/11

– 16 –

Where appliance instructions differ from this manual, follow the appliance instructions.

5. Checkout procedure — before starting the burner

Before firing the burner . . .

Should overheating or an emergency occur, im-

mediately do the following:

• Shut off gas supply valve.

• Under some circumstances power should remain

on for water pumps or blowers. Determine proper

response before attempting start-up.

• If burner fails ignition on several attempts, use

burner blower to purge appliance chamber

before restart.

Checklist before firing . . .

Burner and appliance installed per this manual and appliance

instruction manual?

Burner/appliance installed per all applicable codes?

Installation site has adequate combustion/ventilation air open-

ings and vent system?

Are voltages correct? Burner, appliance and motor correctly

wired per burner and appliance manuals and wiring diagrams?

Gas manifold spud orifices (on gas manifold, item 29, page 5)

sealed with pipe dope and tight?

Gas supply line in good condition, sized and designed correctly?

Gas line connections and fittings tight?

Burner, appliance and all components inspected and in good

condition?

Appliance limit and operating controls properly installed, wired

and adjusted?

Boiler water supply, feed pumps, automatic feeders, and low

water cut-offs properly piped and wired?

Breeching, draft regulator, draft inducer (if required) properly

installed and operational?

Gas train piping and components correctly installed, tested and

verified gas tight?

Vent lines installed when required?

Gas lines purged?

Sufficient gas line pressure present?

Advertising