Check system • start-up burner/appliance – Carlin G3B User Manual

Page 12

Advertising
background image

Model G3B Gas burner — Instruction manual

Carlin part number MNG3B Gas Rev. 03/17/09

12

4. Check system • start-up burner/appliance

Inspect/check system

Before starting the burner and appliance, verify the system has been installed
as directed by this manual and the appliance instructions.

Check gas piping for leaks

Disconnect the burner from the gas supply line if gas line

test pressure will exceed 14 inches w.c. Exposing the burner
combination gas valve to pressure higher than 14 inches w.c.
can damage the valve seat, resulting in potentially unsafe
operation.

You can usually test the gas piping by allowing the line to fi ll with gas to
main regulator outlet pressure.

1. Shut off gas fl ow to all appliances connected to the meter.

2. If test pressure will be less than 14 inches w.c., turn the burner combi-

nation gas valve knob to OFF. If test pressure will be higher than 14
inches, disconnect the burner from the gas line by shutting off the
main manual gas valve installed near the burner (per Figure 5, page 9)
and disconnecting the ground joint union. See warning above.

3. Watch the gas meter dial. For a one half cubic foot per revolution dial,

there should be no movement of the dial for at least 5 minutes. For
larger volumes per revolution, increase this time proportionately.

4. If you detect a gas leak, locate the leak with a soap suds mixture and

repair it. Then test the system for leaks again.

Do not test for leaks with an open fl ame. And do not use

oxygen as a test gas. Either of these could cause an
explosion, resulting in severe personal injury, death or
substantial property damage.

Bleed gas line

Purge all air from the gas line. Purge to outside of the building, NEVER into
the appliance or burner.

Leak test near-burner gas piping

If piping near burner has not already been pressure tested, open main
manual gas valve on supply to burner and smell around area for any signs of
gas. Apply a soap suds mixture to all gas piping joints near burner and check
for any leaks. If any leaks appear, repair before proceeding and retest.

Set air throttle

1. See Figure 8. Loosen air throttle locking nut.

2. Rotate the air throttle plate clockwise to the closed position.

3. Check the air throttle indicator. The “0” position of the indicator should

be even with the end of the air inlet tube. If not, bend the arm slightly
until the indicator reads zero.

4. Rotate air throttle until indicator points to setting given in Figure 4,

page 8.

5. Tighten air throttle locking nut.

Figure 8 Air throttle adjustment

Do not start the burner if you smell gas or if there may be gas

present in the appliance combustion chamber, heat exchanger
or the vent system. An explosion could occur, causing severe
personal injury, death or substantial property damage.

During initial start-up, you must be constantly alert for

emergency conditions such as fuel leaks, electrical malfunc-
tions, etc. Familiarize yourself with the location of manual
shutoff valves and switches so you can quickly use them if
needed.

If the burner fails to ignite, NEVER attempt to manually bypass

the normal sequence of the control, which provides purging
of the combustion chamber.

6. The Figure 4 setting will probably be satisfactory without change. If the

combustion test indicates a need for more or less air, however, you will
have to adjust the throttle accordingly.

Check burner and Honeywell S89C control

Inspect burner thoroughly. Verify all components are secure and burner
is in good condition. Verify all wiring is in place and all components are
secure and in position.

Verify fl ame failure lockout of Honeywell control

1. Install a hose barb fi tting in the combination gas valve outlet pressure tap

and connect with a hose to a U-tube manometer.

2. Close the main manual gas valve and turn the combination gas valve knob

to ON.

3. Turn on power to appliance and set appliance limit(s) to call for heat.

4. Burner motor will start. The Honeywell S89C control will run the blower for

34 seconds (pre-purge and ignitor warm-up). Then the combination gas
valve will open and the “Valve on” light will light. (The manometer should
show almost no pressure, because the main manual gas valve is closed.)

5. After 6 seconds, the S89C will lockout. The ignitor will shut off and the gas

valve will close. Turn off power or interrupt thermostat circuit for 45 seconds.
The control should reset. Turn off power and set controls to stop call for
heat.

6. If lockout does not occur, replace the S89C control.

Advertising