Model G3B Gas burner — Instruction manual

Carlin part number MNG3B Gas Rev. 03/17/09

16

5. Perform checkout procedures • fi ll out certifi cate

(continued)

Verify burner/appliance operation

Check burner/appliance/controls operation

Test operating and limit controls on appliance as specifi ed in appliance

instruction manual.

Check operation of the S89C primary control, forcing lockout by

closing the main manual gas cock and cycling the burner. See page
13 for procedure to reset the control.

Verify burner operation

Start and stop the burner several times, allowing the primary control

to sequence through normal operation. Verify correct operation of
burner and control throughout. See page 13 for burner sequence of
operation.

Verify vent system operation

Verify vent is operating correctly and fl ue products are properly

exhausted from building.

Check operation of barometric damper and spill switch.

If the building contains any exhaust fans or conditions that could

affect vent performance, check burner/appliance/vent operation with
exhaust fans (or other conditions) operating.

Prepare burner for normal operation

Cycle burner off with appliance controls. Then turn off power to the

appliance.

Close the main manual gas valve.

Remove the U-tube manometer line from the combination gas valve

outlet pressure tap hose barb. Remove hose barb and replace 1/8"
NPT pipe plug in tapping.

Verify all components and wires are in place and burner is ready for

operation.

Train the user

Train the user to operate the burner and appliance under normal

conditions. Explain procedure to shut down burner/appliance when
required.

Review the user information section of this manual (and the appliance

manual) with the user.

Verify the user is aware of all procedures specifi ed in the manual.

Verify user will not store or use combustible liquids or materials or

contaminants in the vicinity of the burner/appliance.