For example, a 0-100 psig pressure transducer with a 4-20 mA output
will have a –25 offset.

y=mx+b

100 psi = (100psi / 16mA) x (20mA) +b

100 psi – 125 psi = b

-25 psi = b = ‘Offset

10.1.4 Customize

Menu

The Customize menu is used to configure the transmitter to meet user
needs for local display of flow parameters.

Display

The display parameters are used to customize the displayed units and
appearance of the display.

-

Line 1’ and ‘Line 2’ adjustments set the outputs of those lines to

Totalizer’, ’Flow Rate %’, ‘Flow Rate’, and ‘Blank’.

-

Contrast’ is used to adjust the screen appearance due to lighting

conditions. Normally this is set to 170.

Sensor Setup

-

State’ – used to turn individual sensors ‘On’ or ‘Off’. Normal

operating condition is with all sensors set to ‘On’.

Flow Units

The menu selectable units for ‘Volume’ are ‘gal’ (gallons), ‘l’ (liters),
m

3‘,

(cubic meters), ‘user’ (user defined), ‘iga’ (imperial gallons), ‘ft

3

(cubic feet), ‘ft’ (feet), ‘m’ (meter).

The menu selectable units for ‘Time’ are ‘s’ (second), ‘m’ (minute), ‘h
(hour), ‘d’ (day), ‘user’ (user defined).

In both the ‘Volume’ and ‘Time’ selections custom user labels can be
input by the user by selecting ‘user’ from the menu. The user defined
labels are then input using the ‘User Volume / Time’, ‘Base’, and
Scale Factors’.

Flow Cutoff Range

The flow cutoff range ‘Low End’ and ‘High End’ are used to set the
low end and high end, respectively, of flow rates that will be displayed
on the transmitter. Flow under or over the set points will be displayed
as ‘<Min Flow’, ‘>Max Flow’, as appropriate.

Advertising