FM APPROVAL

NOTE

The NTMOS Gas Detector is designed and approved as a ‘stand alone’ toxic gas detector.

Hazardous Location
Class I, Division 1, Groups B, C, D
Class I, Division 2, Groups A, B, C, D
–40°C to +65°C (Performance verified)
–40°C to +75°C (Haz Loc Rating)
IP66/IP67 (with hydrophobic filter)
IP53 (without hydrophobic filter)

Acidic atmospheres excluded.

Accuracy
Performance tested to ANSI/ISA-92.0.01:
±10% of applied gas concentration or ±2 ppm whichever is greater.

Temperature variation
Performance tested to ANSI/ISA-92.0.01:
–10°C to +50°C, ±5 ppm at 50 ppm of applied gas concentration.
Det-Tronics verified:
–40°C to -10°C, ±10 ppm at 50 ppm of applied gas concentration
+50°C to +65°C, ±8 ppm at 50 ppm of applied gas concentration.

Humidity variation
Performance tested to ANSI/ISA-92.0.01:
5 to 95% RH: ±5 ppm at 50 ppm of applied gas concentration.

Response time (with full Ingress Protection applied)
T50 ≤10.8 seconds with full gas scale applied
T90 ≤33.0 seconds with full gas scale applied.

Mechanical
Model with hydrophobic filter and sinter guard (IP66/IP67)
Model with hydrophobic filter removed and sinter guard (IP53).

Performance tested to ANSI/ISA-92.0.01 – Sample of test requirements

Gas Detected

ANSI/ISA 92.0.01: 1998 (App. A)

H

2

S Requirement

Det-Tronics IP66/IP67 Model NTM

Series Approved Performance

Full Scale Range

10 - 100 PPM full scale

10 - 100 PPM full scale*

Operating Temperature Range

–10°C to +50°C

–40°C to +65°C*

Storage Temperature Range

–35°C to +55°C

–40°C to +65°C*

Test Gas Concentration

45 - 55% of full scale

45 - 55% of full scale

Test Gas Tolerance

1 PPM or 5% of concentration

1

1 PPM or 5% of reading

Accuracy/repeatability (Readout or display) 2 PPM or 10% of reading

1

2 PPM or 10% of reading

Accuracy/repeatability (Alarm-only)

2 PPM or 10% of reading

1

2 PPM or 10% of reading

Alarm setpoint

50% of full scale

10 to 90% of full scale

Time, Response to 20% of Final

20 seconds

5.4 seconds

Time, Response to 50% of Final

45 seconds

10.8 seconds

Time, Response to 90% of Final

60 seconds

33.0 seconds

Time, Recovery to 50% of Initial

180 seconds

6.7 seconds

Time, Recovery to 10% of Initial

90 seconds

16.3 seconds

High Concentration

1000 PPM

1000 PPM

High Concentration Recovery Time

10 minutes

<= 2 minutes

1

Where two values exist (e.g., 3 PPM or 10% of reading), the value providing the widest tolerance should be used.

*In accordance with FMID 3033318.