Figure 2—ntmos detector wired to flexvu model ud10 – Det-Tronics NTMOS IP66/IP67 H2S Gas Detector User Manual

Page 6

Advertising
background image

95-8670

2.1

4

INSTALLATION AND WIRING
1. Determine the best mounting locations for the

detector. Mount the detector with the sensing

element pointing down (18 inches from surfaces

below). The junction box (GDTB or transmitter

housing) is intended for flat-surface mounting, such

as on a wall or post. A spacer or stand-off (1/4 to 1/2

inch) may be needed to allow adequate clearance

for the detector and calibration cup. The junction box

should be electrically connected to earth ground.

NOTE

To ease installation and future removal, use Teflon
tape for the male threads of the detector. The
Lubriplate grease (see Ordering Information for
part number) is used to lubricate the threads on the
junction box cover. The use of silicone grease must
be avoided.

2. Terminate all detector wiring at the proper terminals

and verify that bonding between detector housing-

to-ground terminal is less than 0.1 ohm. Refer to

Table 1 and Figures 2 to 6 for wiring details:

Figure 2—NTMOS Detector Wired to FlexVu Model UD10

NTMOS H2S

DETECTOR

BLACK

RED

GREY

1

YELLOW

WHITE

ORANGE

1

UD10

DISPLAY UNIT

C2448

Sensor Connector

Power Supply Connector

Output Loop

Connector

MODBUS

Connector

R

ela

y Connect

or

P1

J2

J3

J4

P2

4-20 mA +

4-20 mA –

SHIELD

COM

RS485 A

RS.485 B

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

P1-3

P1-2

P1-1

J2-3

J2-2

J2-1

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J3-1

J3-2

J3-3

J3-4

J3-5

P2-6

P2-5

P2-4

P2-3

P2-2

P2-1

1

GREY AND ORANGE WIRES ARE FOR

FACTORY USE ONLY. THEY CAN BE
TAPED OFF IF LOCAL CODES ALLOW,
OR CONNECTED TO THE POWER
SUPPLY MINUS (24 VDC –) OR SHIELD
TERMINALS.

NOTE

UD10 HOUSING MUST BE ELECTRICALLY

CONNECTED TO EARCH GROUND

Figure 3—NTMOS Wired Directly to UD10 via the NTMOS Connector Board

NOTE 1

REMOVE UD10 ELECTRONIC MODULE FOR ACCESS

TO NTMOS CONNECTOR BOARD (NO TOOLS REQUIRED).

NOTE 2

GREY AND ORANGE WIRES FOR FACTORY USE ONLY.

NOTE 3

HOUSINGS MUST BE ELECTRICALLY CONNECTED TO

EARTH GROUND.

UD10

DISPLAY UNIT

B2493

J2

P1

COM 1 (GR

A

Y)

COM 2 (OR

ANGE)

C

AL (YELL

O

W)

R

TN (BLA

CK)

4/20 (WHITE)

24V (RED)

SHIELD

CA

L

RT

N

4/20

24V

CONNECT TO UD10 MODULE’S J3 WITH
FACTORY INSTALLED CABLE

NTMOS CONNECTOR BOARD

NTMOS

H2S DETECTOR

RED

BLA

CK

WHITE

YELL

O

W

GREY

OR

ANGE