Det-Tronics NTMOS IP66/IP67 H2S Gas Detector User Manual

Page 7

Advertising
background image

2.1

95-8670

5

3. Confirm that the power and signal cabling for the

gas detector is the proper size and type, and is

appropriate for the application requirements. After

all electrical connections are made, double check the

terminations against the wiring diagrams to ensure

that all connections are properly terminated.

4. The NTMOS Detector is designed to operate at 24

Vdc nominally. Measure the delivered voltage at the

detector, especially for long cable runs, to ensure

that possible voltage drops have not compromised

the necessary 24 Vdc supply voltage. This

should be considered during system design and

commissioning.

NOTE

Do not apply power to the system with the junction
box cover removed unless the area has been
de‑classified.

5. After confirming that the detector is properly installed

and wired, all electrical terminations are properly

made, and proper operating voltage is provided to

the detector, the installer may conduct the startup

procedure.

Figure 5—NTMOS Detector Wired to U9500 Infiniti Transmitter

E2361

INFINITI TRANSMITTER

NO

COM

NC

S


+

RESET

CA
L

FA

UL
T RELA

Y

PO
WER

PW

IN

GREY

OR

ANGE

BLA

CK

RED

YELL

O

W

WHITE

NTMOS H2S

DETECTOR

Figure 4—NTMOS Detector Wired to GDTB Termination Box for Stand-

Alone Operation

NOTES:

1 CUSTOMER SUPPLIED NORMALLY OPEN
MOMENTARY CLOSURE SWITCH CAN BE
USED TO INITIATE CALIBRATION. MOMENTARY
CONNECTION TO POWER SUPPLY MINUS
(24 VDC -) INITIATES THE CALIBRATION
SEQUENCE.

2 PLACE MAGNET AT THIS
LOCATION APPROXIMATELY ONE
INCH ABOVE MOUNTING
SURFACE TO ACTUATE SWITCH.

C2447

GDTB TERMINATION BOX

NTMOS H2S

DETECTOR

RED

+24

RET

4-20

CA

L

COMM 1

COMM 2

+24

RET

4-20

CA

L

COMM 1

COMM 2

BLA

CK

WHITE

YELL

O

W

GREY

OR

ANGE

24 VDC +

24 VDC –

4-20 MA

CAL SWITCH

1

INTERNAL
MAGNETIC
REED SWITCH

2

Figure 6—NTMOS Detector Wired to Model R8471B Controller through

the GDTB Termination Box

CURRENT OUTPUT

CHASSIS GROUND

POWER

SENSOR

EXTERNAL RESET

HIGH ALARM

HIGH ALARM / OC

AUX. ALARM

AUX. ALARM / OC

LOW ALARM

LOW ALARM / OC

FAULT

FAULT / OC

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

+

+

+

18 TO 32

VDC

POWER

SIGNAL

RESET

24 VDC

+

2

B2535

GDTB

TERMINATION BOX

R8471B CONTROLLER

NTMOS H2S

DETECTOR

4 TO 20 MA

24 VDC –

24 VDC +

+

4-20 MA

NOTES:
1. TAPE OFF ALL UNUSED NTMOS DETECTOR

LEADS TO PREVENT SHORTING.

2. REFER TO FIGURE 4 FOR ADDITIONAL

WIRING INFORMATION WHEN USING

THE GDTB WITH THE NTMOS DETECTOR.