Det-Tronics X5200 UVIR SIL 2 Certified Flame Detectors SAFETY MANUAL User Manual
Page 2
![background image](/manuals/557646/2/background.png)
1.1
95-8672
2
DESIGN
The X2200/X9800/X5200 flame detector is classified
as a Type B smart device according to IEC61508.
The standard model provides an isolated 4‑wire,
0‑20 mA output, together with on‑board Alarm and
Fault relay contacts. These outputs serve to indicate
normal operating condition of the detector, fault, or the
presence of a flame alarm. The X2200/X9800/X5200
contains extensive self‑diagnostics and is programmed
to send the current output to a specified state (0 mA, 1
mA, or 2 mA) upon internal detection of a failure or fault
condition.
HART communication is available as an option. The
HART option allows the operator to monitor the status
of the detector, determine factory settings, adjust
field settings, and initiate field tests. For specific
information regarding HART communication, refer to
the appropriate HART Addendum:
X2200 UV Flame Detector
95‑8638
X9800 IR Flame Detector
95‑8637
X5200 UVIR Flame Detector
95‑8636
NOTE
All configuration changes to the X2200/X9800/
X5200 must be verified by the user via a proof
test, power cycle and re-check of settings, or
other appropriate method.
The X2200/X9800/X5200 is designed for operation with
a supply voltage from 18‑30 volts DC. Proper operation
outside this range cannot be assumed.
Safety‑Certification of the X2200/X9800/X5200 includes:
• Analog Output
• Relay Output
• HART Output as non-interfering.
Safety‑Certification of the X2200/X9800/X5200 does
not
include:
• Pulse Output
• EQP LON Output version
• RS-485 Modbus signal.
VALID INPUT RANGE
Fault annunciation is provided on the 0‑20 mA signal
output loop by signaling to a 1 mA, 2 mA, or 3 mA current
output level. The receiving device must be programmed
to indicate a fault condition when current levels reach
over‑current (> 21 mA) or undercurrent (< 2.25 mA).
NOTE
The X2200/X9800/X5200 analog signal and relay
outputs are not safety-rated during detector
warm-up or signal output loop testing (including
proof testing). Alternative means should be used
at the job site to ensure facility safety during
these activities.
DIAGNOSTIC RESPONSE TIME
The X2200/X9800/X5200 will perform all critical
diagnostic functions within 58 minutes, worst case
diagnostic detection time. The user must not configure
the automatic oi test interval and failure annunciation
count combination to be greater than 58 minutes
(default setting is one minute intervals, with failure
annunciation after three failed oi tests).
OPTICAL INTEGRITY TEST
The oi test is designed to generate a fault when the
unit’s detection range has been reduced by 50% or
more. This factor should be carefully considered
during detector placement with regard to the required
safety function.
CERTIFICATION
The X2200/X9800/X5200 Safety‑Certified version is
certified to IEC61508:2010 for single input use in low
demand SIL 2 Safety Instrumented Systems.
SAFETY-CERTIFIED PRODUCT IDENTIFICATION
Safety Certification of all X2200/X9800/X5200 models
meeting SIL 2 safety standards is clearly identified on
the product label.
INSTALLATION
NOTE
For complete information regarding performance,
installation, operation, maintenance and
specifications, refer to the appropriate instruction
manual:
X2200 UV Flame Detector
95-8549
X9800 IR Flame Detector
95-8554
X5200 UVIR Flame Detector
95-8546
Tools Required:
• 14 mm hexagonal wrench