DESIGN
The X2200/X9800/X5200 flame detector is classified

as a Type B smart device according to IEC61508.

The standard model provides an isolated 4‑wire,

0‑20 mA output, together with on‑board Alarm and

Fault relay contacts. These outputs serve to indicate

normal operating condition of the detector, fault, or the

presence of a flame alarm. The X2200/X9800/X5200

contains extensive self‑diagnostics and is programmed

to send the current output to a specified state (0 mA, 1

mA, or 2 mA) upon internal detection of a failure or fault

condition.

HART communication is available as an option. The

HART option allows the operator to monitor the status

of the detector, determine factory settings, adjust

field settings, and initiate field tests. For specific

information regarding HART communication, refer to

the appropriate HART Addendum:
X2200 UV Flame Detector

95‑8638

X9800 IR Flame Detector

95‑8637

X5200 UVIR Flame Detector

95‑8636

NOTE

All configuration changes to the X2200/X9800/
X5200 must be verified by the user via a proof
test, power cycle and re-check of settings, or
other appropriate method.

The X2200/X9800/X5200 is designed for operation with

a supply voltage from 18‑30 volts DC. Proper operation

outside this range cannot be assumed.

Safety‑Certification of the X2200/X9800/X5200 includes:
• Analog Output
• Relay Output
• HART Output as non-interfering.

Safety‑Certification of the X2200/X9800/X5200 does

not

include:

• Pulse Output
• EQP LON Output version
• RS-485 Modbus signal.

VALID INPUT RANGE
Fault annunciation is provided on the 0‑20 mA signal

output loop by signaling to a 1 mA, 2 mA, or 3 mA current

output level. The receiving device must be programmed

to indicate a fault condition when current levels reach

over‑current (> 21 mA) or undercurrent (< 2.25 mA).

NOTE

The X2200/X9800/X5200 analog signal and relay
outputs are not safety-rated during detector
warm-up or signal output loop testing (including
proof testing). Alternative means should be used
at the job site to ensure facility safety during
these activities.

DIAGNOSTIC RESPONSE TIME
The X2200/X9800/X5200 will perform all critical

diagnostic functions within 58 minutes, worst case

diagnostic detection time. The user must not configure

the automatic oi test interval and failure annunciation

count combination to be greater than 58 minutes

(default setting is one minute intervals, with failure

annunciation after three failed oi tests).

OPTICAL INTEGRITY TEST
The oi test is designed to generate a fault when the

unit’s detection range has been reduced by 50% or

more. This factor should be carefully considered

during detector placement with regard to the required

safety function.

CERTIFICATION
The X2200/X9800/X5200 Safety‑Certified version is

certified to IEC61508:2010 for single input use in low

demand SIL 2 Safety Instrumented Systems.

SAFETY-CERTIFIED PRODUCT IDENTIFICATION
Safety Certification of all X2200/X9800/X5200 models

meeting SIL 2 safety standards is clearly identified on

the product label.

INSTALLATION

NOTE

For complete information regarding performance,
installation, operation, maintenance and
specifications, refer to the appropriate instruction
manual:

X2200 UV Flame Detector

95-8549

X9800 IR Flame Detector

95-8554

X5200 UVIR Flame Detector

95-8546

Tools Required:
• 14 mm hexagonal wrench