Det-Tronics X5200 UVIR SIL 2 Certified Flame Detectors SAFETY MANUAL User Manual
Page 6
![background image](/manuals/557646/6/background.png)
PRODUCT CERTIFICATIONS
FM, CSA, ATEX, CE, IECEx, and exida.
Refer to the Instruction Manual for details.
FMEDA Report available.
For complete information regarding performance,
installation, operation, maintenance and specifications
of the X2200/X9800/X5200, refer to the appropriate
instruction manual:
X2200 UV Flame Detector
95‑8549
X9800 IR Flame Detector
95‑8554
X5200 UVIR Flame Detector
95‑8546
TERMS AND DEFINITIONS
EQP
Eagle Quantum Premier System
EQPSL/SLC Eagle Quantum Premier Safety Loop /
Signaling Line Circuit
FMEDA
Failure Mode Effects and Diagnostics
Analysis
HART
Highway Addressable Remote
Transducer
HFT
Hardware Fault Tolerance
LFL
Lower Flammable Limit
PFD
Probability of Failure on Demand
(Probability of Dangerous Failure)
PFDavg
Average Probability of Failure on
Demand
SFF
Safe Failure Fraction
SIF
Safety Instrumented Function
SIL
Safety Integrity Level
SIS
Safety Instrumented System
X2200
Ultraviolet Flame Detector
X9800
Infrared Flame Detector
X5200
Ultraviolet and Infrared Flame
Detector
Detector Electronics Corporation
6901 West 110th Street • Minneapolis, Minnesota 55438 USA
Operator: (952) 941‑5665 or (800) 765‑FIRE
Customer Service: (952) 946-6491 • Fax (952) 829-8750
http://www.det-tronics.com • E-mail: [email protected]
Specifications subject to change without notice.
Det-Tronics and the DET-TRONICS logo are registered trademarks or
trademarks of Detector Electronics Corporation in the United States, other
countries, or both. Other company, product, or service names may be
trademarks or service marks of others.
©Copyright Detector Electronics Corporation 2011. All rights reserved.
R
EG
IST
ERE
D BY UL AN
D B
SI
NO
. A2305 • NO. 2582
6
ISO 9001
RE
GIS
TERED FIRM
R
EG
IS
TERED FIR
M
Failure Category
l
sd
l
su
2
l
dd
l
du
SFF
3
X2200 Analog Output
0
75
704
61
92.7%
X2200 Analog Output w HART
0
67
877
73
92.8%
X2200 Relay
208
78
501
72
91.6%
X9800 Analog Output
0
93
628
68
91.4%
X9800 Analog Output w HART
0
84
800
80
91.7%
X9800 Relay
220
95
412
79
90.2%
X5200 Analog Output
0
98
834
74
92.6%
X5200 Analog Output w HART
0
90
1007
86
92.7%
X5200 Relay
248
102
591
85
91.7%
IEC 61508 Failure Rates in FIT
1
1
FIT = 1 Failure / 10
9
Hours
2
It is important to realize that the No Effect failures are no longer included in the Safe Undetected failure category according to
IEC 61508, ed2, 2010.
3
Safe Failure Fraction needs to be calculated on (sub)system level.
FM
APPROVED
®
FM
APPROVED
®
FM
APPROVED
®
95-8672