Det-Tronics X5200 UVIR SIL 2 Certified Flame Detectors SAFETY MANUAL User Manual

Page 6

Advertising
background image

PRODUCT CERTIFICATIONS

FM, CSA, ATEX, CE, IECEx, and exida.

Refer to the Instruction Manual for details.

FMEDA Report available.

For complete information regarding performance,

installation, operation, maintenance and specifications

of the X2200/X9800/X5200, refer to the appropriate

instruction manual:
X2200 UV Flame Detector

95‑8549

X9800 IR Flame Detector

95‑8554

X5200 UVIR Flame Detector

95‑8546

TERMS AND DEFINITIONS

EQP

Eagle Quantum Premier System

EQPSL/SLC Eagle Quantum Premier Safety Loop /

Signaling Line Circuit

FMEDA

Failure Mode Effects and Diagnostics

Analysis

HART

Highway Addressable Remote

Transducer

HFT

Hardware Fault Tolerance

LFL

Lower Flammable Limit

PFD

Probability of Failure on Demand

(Probability of Dangerous Failure)

PFDavg

Average Probability of Failure on

Demand

SFF

Safe Failure Fraction

SIF

Safety Instrumented Function

SIL

Safety Integrity Level

SIS

Safety Instrumented System

X2200

Ultraviolet Flame Detector

X9800

Infrared Flame Detector

X5200

Ultraviolet and Infrared Flame

Detector

Detector Electronics Corporation

6901 West 110th Street • Minneapolis, Minnesota 55438 USA

Operator: (952) 941‑5665 or (800) 765‑FIRE

Customer Service: (952) 946-6491 • Fax (952) 829-8750

http://www.det-tronics.com • E-mail: [email protected]

Specifications subject to change without notice.

Det-Tronics and the DET-TRONICS logo are registered trademarks or
trademarks of Detector Electronics Corporation in the United States, other
countries, or both. Other company, product, or service names may be
trademarks or service marks of others.

©Copyright Detector Electronics Corporation 2011. All rights reserved.

R

EG

IST

ERE

D BY UL AN

D B

SI

NO

. A2305 • NO. 2582

6

ISO 9001

RE

GIS

TERED FIRM

R

EG

IS

TERED FIR

M

Failure Category

l

sd

l

su

2

l

dd

l

du

SFF

3

X2200 Analog Output

0

75

704

61

92.7%

X2200 Analog Output w HART

0

67

877

73

92.8%

X2200 Relay

208

78

501

72

91.6%

X9800 Analog Output

0

93

628

68

91.4%

X9800 Analog Output w HART

0

84

800

80

91.7%

X9800 Relay

220

95

412

79

90.2%

X5200 Analog Output

0

98

834

74

92.6%

X5200 Analog Output w HART

0

90

1007

86

92.7%

X5200 Relay

248

102

591

85

91.7%

IEC 61508 Failure Rates in FIT

1

1

FIT = 1 Failure / 10

9

Hours

2

It is important to realize that the No Effect failures are no longer included in the Safe Undetected failure category according to
IEC 61508, ed2, 2010.

3

Safe Failure Fraction needs to be calculated on (sub)system level.

FM

APPROVED

®

FM

APPROVED

®

FM

APPROVED

®

95-8672