OPERATION, MAINTENANCE, INSPECTION AND
PROOF TESTING
Tools Required:
• Magnetic oi test tool (p/n 102740‑002)
• Window cleaner (p/n 001680-001 or isopropanol)
• Lens tissue and cotton swabs
• 4 mm flat blade screwdriver
After normal installation and start‑up have been
completed as recommended within the instruction
manual, Proof Tests must be performed for every Safety‑
Certified X2200/X9800/X5200 detector installed.
Personnel performing Proof Test procedures shall be
competent to perform the task. All Proof Test results
must be recorded and analyzed. Any corrective actions
taken must be documented in the event that an error is
found in the safety functionality. The Proof Tests must
be performed at a frequency as shown in Table 1.
WARNING
Failure to perform the specified testing and
inspection may lower or void the SIL rating for the
product or system.
VISUAL FIELD INSPECTION PROOF TEST
Visual inspection of all Safety‑Certified X2200/X9800/
X5200 flame detectors shall be conducted as needed
to confirm that there are no obstructions in the optical
field of view. Corrective action will include removal of
such impediments should they exist.
Completion of Visual Field Inspection Proof test will be
recorded and documented in the SIS logbook.
DETECTOR RESPONSE MAG
oi
PROOF TEST
WARNING
Any external alarm equipment, systems or
signaling devices that could be automatically
initiated by performing this test must be disabled
or bypassed before performing this test!
Tools Required:
• Magnetic oi test tool (part number 102740‑002)
All flame detectors must be performance tested using
the Mag oi Procedure as described in the Magnetic
oi / Manual oi section of the instruction manual and
inspected to ensure that they are capable of providing
expected performance and protection. Note that
the Mag oi Procedure and Manual oi Tests are not
interference free. During these tests the unit is not
performing normal flame detection functions. Model
X2200/X9800/X5200 provides an onboard status LED,
which indicates Green color when internal operational
parameters are normal.
To indicate a successful proof test, the LED changes to
a Red color, the Alarm and Auxiliary relays change state
to indicate an alarm condition, and the current output
indicates 20 mA. These results should be verified on
the control device.
To indicate an unsuccessful proof test, the LED changes
to Yellow, the Fault relay becomes de‑energized, and
the current output indicates 2 mA. The fault indication
can be reset by momentarily applying the magnet or
manual oi switch.
Proof Test Name
Commissioning
Frequency
Visual Field Inspection Proof Test
Yes
As needed, depending on level and
type of contaminants present
Detector Response Mag
oi Proof Test
Yes
Yearly
Table 1—Frequency of Proof Tests