OPERATION, MAINTENANCE, INSPECTION AND
PROOF TESTING
Tools Required:
• Magnetic oi test tool (p/n 102740‑002)
• Window cleaner (p/n 001680-001 or isopropanol)
• Lens tissue and cotton swabs
• 4 mm flat blade screwdriver

After normal installation and start‑up have been

completed as recommended within the instruction

manual, Proof Tests must be performed for every Safety‑

Certified X2200/X9800/X5200 detector installed.

Personnel performing Proof Test procedures shall be

competent to perform the task. All Proof Test results

must be recorded and analyzed. Any corrective actions

taken must be documented in the event that an error is

found in the safety functionality. The Proof Tests must

be performed at a frequency as shown in Table 1.

WARNING

Failure to perform the specified testing and
inspection may lower or void the SIL rating for the
product or system.

VISUAL FIELD INSPECTION PROOF TEST
Visual inspection of all Safety‑Certified X2200/X9800/

X5200 flame detectors shall be conducted as needed

to confirm that there are no obstructions in the optical

field of view. Corrective action will include removal of

such impediments should they exist.

Completion of Visual Field Inspection Proof test will be

recorded and documented in the SIS logbook.

DETECTOR RESPONSE MAG

oi

PROOF TEST

WARNING

Any external alarm equipment, systems or
signaling devices that could be automatically
initiated by performing this test must be disabled
or bypassed before performing this test!

Tools Required:
• Magnetic oi test tool (part number 102740‑002)

All flame detectors must be performance tested using

the Mag oi Procedure as described in the Magnetic

oi / Manual oi section of the instruction manual and

inspected to ensure that they are capable of providing

expected performance and protection. Note that

the Mag oi Procedure and Manual oi Tests are not

interference free. During these tests the unit is not

performing normal flame detection functions. Model

X2200/X9800/X5200 provides an onboard status LED,

which indicates Green color when internal operational

parameters are normal.

To indicate a successful proof test, the LED changes to

a Red color, the Alarm and Auxiliary relays change state

to indicate an alarm condition, and the current output

indicates 20 mA. These results should be verified on

the control device.

To indicate an unsuccessful proof test, the LED changes

to Yellow, the Fault relay becomes de‑energized, and

the current output indicates 2 mA. The fault indication

can be reset by momentarily applying the magnet or

manual oi switch.

Proof Test Name

Commissioning

Frequency

Visual Field Inspection Proof Test

Yes

As needed, depending on level and

type of contaminants present

Detector Response Mag

oi Proof Test

Yes

Yearly

Table 1—Frequency of Proof Tests