FAULT/FAILURE ACTION PLAN
In the event of a non‑alarm condition result with the Mag

oi test, the standard Maintenance and Troubleshooting

procedures listed in the instruction manual must be

followed. In the event that the condition cannot be

resolved, the standard Device Repair and Return

procedures listed in the instruction manual must be

followed.

Any and all failures to successfully complete the alarm

test must be recorded and documented in the SIS

logbook.

WARNING

Any external alarm equipment, systems or
signaling devices that were disabled must be
re-activated at the conclusion of proof testing
activities.

PRODUCT REPAIR
The X2200/X9800/X5200 is not field‑repairable and any

internal device repairs must be conducted at the factory.

No firmware changes are permitted or authorized. All

failures indicated by internal diagnostics or Proof Tests

that cannot be resolved through the troubleshooting

and maintenance procedures described in the manual

must be reported to the manufacturer.

OPERATING, ENVIRONMENTAL AND
PERFORMANCE SPECIFICATIONS
The operating temperature range for the Safety

Certified X2200/X9800/X5200 is –40C to +75C. The

Safety‑Certified X2200/X9800/X5200 product versions

fully comply with, and must be operated in accordance

with the functional and performance specifications

provided in the corresponding instruction manual. A 24

hour mean time to repair should be assumed for safety

availability calculations.

SPARE PARTS

Refer to the spare parts section of the instruction

manual. Safety certification is based on a sufficient

number of spares to achieve a 24 hour mean time to

repair.

CERTIFICATION AND FAILURE RATE DATA
All Safety‑Certified X2200/X9800/X5200 models are

certified compliant to:

IEC61508: 2010
Type B Device
Systematic Capability: SIL 2 certified
HFT: 0
Low Demand Mode
PFDavg should be calculated for any safety

instrumented function using the X2200/X9800/X5200.

(Refer to FMEDA report for necessary information,

including DU rate).
Safety Accuracy:

Not applicable.

Safety Response Time: See appendix A of the

corresponding instruction

manual for response time

details.

Product Life X2200:

25‑53 years, based on

manufacturer data.

Product Life X9800:

21‑43 years, based on

manufacturer data.

Product Life X5200:

10‑78 years, based on

manufacturer data.

All failure rate data for SIL verification is in the FMEDA

report, which is available upon request.