Det-Tronics X3301 Multispectrum IR Flame Detector with HART User Manual

Page 12

Advertising
background image

95-8577

10

3.1

STATUS INFO MENU
This menu (read only) shows extensive status information about the detector.

1) Warmup (Y/N)

Device is in the power-up time delay (warm-up) mode.

2) Fire (Y/N)

Indicates “Y” if the device is in a fire alarm status — analog output is at

20

mA, fire alarm

relay is actuated and LED is red.

3) Auto

oi Fault (Y/N) Automatic

oi Fault. Check viewing windows and oi reflector plate for cleanliness.

4) Dim Detect Fault (Y/N)

Diminished Detection Fault. Excessive background IR radiation. Eliminate IR interference

and/or re-aim/orient detector.

5) Detect Disable Flt (Y/N)

Flame detector function has been disabled. Check viewing windows for cleanliness and/

or presence of excessive background IR signal.

6) Snsr Hdwr Fault (Y/N)

Sensor hardware fault.

7) HIB Hdwr Fault (Y/N)

HART Interface Board hardware fault.

8) Int Comm Fault

Internal communication fault.

9) Incompatible Flt

Sensor module firmware version is not compatible with HART Interface Board.

10) Voltage Fault (Y/N)

Detector operating voltage is out of tolerance.

11) Hardware Menu

Refer to sub-menu.

12)

oi Menu

Refer to sub-menu.

Device Info Menu

1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu

X3301 Root Menu

1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu

Status Info Menu

1) Warmup (Y/N)
2) Fire (Y/N)
3) Auto Oi Fault (Y/N)
4) Dim Detect Fault (Y/N)
5) Detect Disable Flt (Y/N)
6) Snsr Hdwr Fault (Y/N)
7) HIB Hdwr Fault (Y/N)
8) Int Comm Fault
9) Incompatible Flt
10) Voltage Fault (Y/N)
11) Hardware Menu
12) Oi Menu