Det-Tronics X3301 Multispectrum IR Flame Detector with HART User Manual

Page 15

Advertising
background image

13

95-8577

3.1

DETECTOR SETTINGS
This menu shows factory settings relating to relay operation, detector sensitivity and response.

1) Fire Relay (L/NL)

Fire relay contacts, latching (L) or non-latching (NL).

2) Fire Relay (NDE/NE)

Fire relay coil, normally de-energized (NDE) or normally energized (NE).

3) Fault Relay (L/NL)

Fault relay contacts, latching (L) or non-latching (NL).

4) Fault Relay (NDE/NE)

Fault relay coil, normally de-energized (NDE) or normally energized (NE).

5) Aux Relay (L/NL)

Auxiliary relay contacts, latching (L) or non-latching (NL).

6) Aux Relay (NDE/NE)

Auxiliary relay coil, normally de-energized (NDE) or normally energized (NE).

7) Sensitivity (VH/H/M/L)

Detector sensitivity setting: Very high, High, Medium, or Low.

8) Response (

.5/3/6/9

)

Fire alarm processing time in seconds.

HISTORY MENU
This menu provides historical information about the detector. Up to

32

events in each of the three categories will be

kept in non-volatile memory. When the log is full, the oldest event will be overwritten. The most recent event will be

displayed first.

1) Alarm Log

Scroll through

32

Alarm Logs with time, date and temperature stamp.

2) Fault Log

Scroll through

32

Fault Logs with time, date and temperature stamp.

3) General Log

Scroll through

32

General Logs with time, date and temperature stamp.

History Menu

1) Alarm Log
2) Fault Log
3) General Log

Device Info Menu

1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu

X3301 Root Menu

1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu

Device Info Menu

1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu

X3301 Root Menu

1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu

Detector Settings

1) Fire Relay (L/NL)
2) Fire Relay (NDE/NE)
3) Fault Relay (L/NL)
4) Fault Relay (NDE/NE)
5) Aux Relay (L/NL)
6) Aux Relay (NDE/NE)
7) Sensitivity (VH/H/M/L)
8) Response (.5/3/6/9)

Advertising