Det-Tronics X3301 Multispectrum IR Flame Detector with HART User Manual

Page 13

Advertising
background image

11

95-8577

3.1

HARDWARE MENU

1) Heater Power

Actual heater power (

0

to

100%

). Heater prevents condensation and icing on the detector

optics.

2) Heater Setpoint

Maximum amount of heater power allowed (in percent of full power).

3) Temperature

Actual internal temperature of detector.

4) Temp Setpoint

Internal target temperature that the heater will attempt to maintain (in degrees C).

5) Temp Range Fault

Detector integral temperature out of range — Operating range: –

40°

F to +

167°

F

(–

40°

C to +

75°

C).

6) Voltage

Actual detector supply voltage (must be

18

to

30

Vdc).

7) Volt Range Fault

Supply voltage is out of range. Operating voltage must be

18

to

30

Vdc.

Hardware Menu

1) Heater Power
2) Heater Setpoint
3) Temperature
4) Temp Setpoint
5) Temp Range Fault
6) Voltage
7) Volt Range Fault

Device Info Menu

1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu

X3301 Root Menu

1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu

Status Info Menu

1) Warmup (Y/N)
2) Fire (Y/N)
3) Auto Oi Fault (Y/N)
4) Dim Detect Fault (Y/N)
5) Detect Disable Flt (Y/N)
6) Snsr Hdwr Fault (Y/N)
7) HIB Hdwr Fault (Y/N)
8) Int Comm Fault
9) Incompatible Flt
10) Voltage Fault (Y/N)
11) Hardware Menu
12) Oi Menu