Det-Tronics OPECL Infrared Hydrocarbon Gas Detector SAFETY MANUAL User Manual

Page 2

Advertising
background image

1.2

95-8665

2

DESIGN
The Model OPECL Open Path Eclipse Gas Detector is

an infrared hydrocarbon gas detector that is classified

as Type B smart device according to IEC61508. It

provides an isolated 4-wire 4-20 mA output that is

proportional to hydrocarbon vapor concentrations from

0-5 LFL-meters. The OPECL contains extensive self-

diagnostics and is programmed to send the current

output to a specified failure state upon internal detection

of a failure (see OPECL instruction manual for fault

output level details). Optional Alarm and Fault relay

contact outputs are available in addition to the analog

signal output, and can be programmed in the field by

the user. The Safety Certification for the OPECL Open

Path Eclipse Gas Detector includes both the standard

version with analog output only and the version with

optional relay outputs. The relay output and analog

output are not to be used in combination for the safety

function.

Safety-Certification of the OPECL Open Path Eclipse

includes:
• the 4-20 mA output
• the Fault and High Alarm Relay outputs

RS-485 Modbus signal output is not part of the SIL

certification.

The HART communication protocol is non-interfering

and is to be used for diagnostics within the SIL 2

safety loop in the Safety operation mode. Diagnostics

are defined as read only information. Local HART

communication with the OPECL IR Gas Detector via the

onboard intrinsically-safe communication port using a

handheld HART field communicator, or AMS program

connected to the 4-20 mA output, is acceptable. Proper

analog signal loop resistance must be installed as

documented in the instruction manual to enable local

HART communication.

VALID INPUT RANGE
OPECL fault annunciation is provided on the 4-20 mA

signal output loop by signaling to a specific mA current

output level. The receiving device must be programmed

to indicate a fault condition when current levels reach

overcurrent (> 20.5 mA) or undercurrent (< 3.8 mA).

NOTE

The OPECL analog signal and relay outputs
are not safety-rated during detector warm-up,
alignment mode, calibration mode, or during
signal output loop testing. Alternative means
should be used at the job site to ensure facility
safety during these activities.

DIAGNOSTIC RESPONSE TIME
The OPECL Infrared Gas Detector will perform all

critical diagnostic functions within 58 minutes, worst

case diagnostic detection time.

CERTIFICATION
The OPECL Safety-Certified version is certified by

exida

®

to IEC61508 for single input use in low demand,

SIL 2 Safety Instrumented Systems.

SAFETY-CERTIFIED PRODUCT IDENTIFICATION
The model number printed on the label will include the

character “T” in the model number string “Approval

Agency Type” section, indicating exida

®

approval for

SIL 2 standard. Example: Model OPECLS2M00T1S.

INSTALLATION

NOTE

For complete information regarding performance,
installation, operation, maintenance and
specifications of Model OPECL, refer to
instruction manual 95-8556.

No special or additional detector installation

requirements exist above and beyond the standard

installation practices documented in the Model OPECL

instruction manual.

The operating temperature range for the Safety Certified

OPECL is –40°C to +60°C. Other environmental

operating specifications are applicable as published in

the general specifications section in the Model OPECL

instruction manual.

The OPECL operating power distribution system should

be designed and installed so the terminal voltage does

not drop below 18 Vdc when measured at any specific

location. The maximum current limit per transmitter or

receiver must be less than 2 amperes. The external

system providing power to the OPECL must have over-

voltage protection that ensures supply voltage does not

exceed 30 Vdc.