Common Misuse Scenarios
• Do not install the OPECL on unstable or vibration

prone structures; a 3 meter maximum height is

recommend when using a vertical post.

• Do not install the OPECL below the height of typical

human activity unless absolutely necessary in order

to prevent nuisance beam block faults.

• Do not install an OPECL receiver where multiple

transmitters are in the line of sight - this is a common

concern for pipeline system installations.

NOTE

The above common misuse scenarios will cause
the OPECL to annunciate a fault if the condition is
severe enough to compromise the safety function.

START-UP AND COMMISSIONING

Commissioning Personnel
The Safety Certified OPECL gas detector can be

commissioned by any qualified person with knowledge

of gas detection instruments and the configuration

device being used. Refer to the Start-Up, Alignment

and Calibration sections provided in the OPECL

instruction manual.

Configuration
Digital communication with the Open Path Eclipse is

necessary to monitor internal status and to modify the

factory settings. Appendix A of the OPECL instruction

manual provides guidance on establishing HART

communication, and describes the communication

menu structure when using the Open Path Eclipse with

the HART Handheld Communicator.

NOTE

Prior to device configuration (setting alarm
thresholds, latch/non-latch function, etc.) all
alarm outputs must be bypassed. The device is
not safety certified during configuration change
activities.

Relay Configuration Requirements
Only the OPECL gas detector’s High Alarm and Fault

relay outputs may be used as part of a Safety Certified

system. The end user must provide transient and

current limiting on the output contacts of the relays.

The maximum relay contact output must be limited to

5 amperes at 30 Vdc. The load must be a resistive

load. The user must protect against transients by using

standard protection methods such as proper grounding

of shielded wire and separation of relay load wires from

other lines carrying rapidly switched high current (e.g.

large motor power supply lines).

Configuration Protection
Upon completion of installation and commissioning,

it is recommended to password-protect the OPECL

programming and setup function using a HART Field

Communicator or AMS program to prevent accidental

or deliberate change of detector configuration data

during normal operation.

OPERATION, MAINTENANCE, INSPECTION AND
PROOF TESTING
All normal installation, start-up, and field calibration

recommendations as documented in the STARTUP

section of the OPECL instruction manual are applicable

to the Safety Certified OPECL gas detector.

Safety-Certified OPECL gas detectors require additional

Proof testing to be performed in all cases.

Personnel performing Proof Test procedures shall be

competent to perform the task. All proof test results

must be recorded and analyzed. Any corrective actions

taken must be documented in the event that an error is

found in the safety functionality. The Proof tests must be

performed at a frequency as shown in Table 1.

WARNING

Failure to perform the specified testing and
inspection may lower or void the SIL rating for the
product or system.

OPECL Proof Test Name

Commissioning

Frequency per Year

Gas Response Proof Test

Yes

1

Output Response Proof Test

Yes

1

Table 1—Frequency for Performing Proof Tests