GAS RESPONSE PROOF TEST

WARNING

Any external alarm equipment, systems or
signaling devices that could be automatically
initiated by performing this test must be disabled
or bypassed before performing this test!

Gas Test Cell Method (Recommended)
Tools Required: Gas Test Cell provided by Det-Tronics,

P/N: 009246-001 (Low Range) or

P/N: 009246-002 (High Range)

The Gas Cell provides a means of testing the operation

of the Model OPECL IR Gas Detector for response to

actual gas. The gas cell is typically used to verify the

factory calibration of the OPECL.

The gas cell has a known optical length and has

infrared transparent windows on both ends. When filled

with 100% v/v gas, it contains a specific LFL-m amount

of gas. When the gas cell is placed in the beam of the

open path detector, the detector output will rise to a

specific value.

The gas cell is not intended for routine use. It does,

however, demonstrate in a very direct way the response

of the detector to hydrocarbons along with the resulting

control action. This is particularly useful when required

by regulatory authorities.

For complete information regarding proper use of the

Gas Cell and testing of the OPECL detector, refer to

manual number 95-8591.

Optical Test Film Method
Tools Required: System Test Film provided by Det-Tronics

P/N: 007902-002

(0.75-1.5 LFL-meter signal output) or

P/N: 007902-003

(1.9-2.5 LFL-meter signal output)

Proper operation can be confirmed by placing an

optical test film into the light beam and checking for

the appropriate signal output level. Alarm conditions,

if present, should clear when the test film is removed

from the beam.

When the test film is in the light beam path of the

detector, inspection of proper analog signal level output

can be made by reading the analog signal output

displayed on the control device. Criteria for inspection

pass is a response signal within the range 0.75-1.5 LFL-

meters for p/n 007902-002 or 1.9-2.5 LFL-meters for

p/n 007902-003. If response is not within acceptable

limits, refer to the Fault/Failure Action Plan.

Zero Calibration
Tools Required: Magnet

Zero Calibration shall be conducted when required

as documented in the Calibration section of the

OPECL instruction manual. It is permissible to initiate

the Zero Calibration using the onboard magnetic

calibration switch, digital communication via MODBUS

communication, or the remote calibration line. In

all cases, the model OPECL gas detector should be

allowed to warm up for one hour minimum before

conducting calibration.

NOTE

The last ten (10) Calibration procedures are
logged with a time stamp (operating hour units)
in the OPECL onboard memory. In addition,
completion of Calibration procedures will be
recorded and documented in the SIS logbook.

Successful completion of the Gas Response Proof Test

must be recorded and documented in the SIS logbook.