1.2

95-8665

5

OUTPUT RESPONSE PROOF TEST

NOTE

The requirements for the Output Response Proof
Test can be waived for the 4-20 mA output if
a successful Gas Response Proof Test was
completed using the 4-20 mA output during the
required time frame. Details must be recorded in
the SIS logbook.

4-20 mA Output Model
1. Inhibit alarm response at the control device.

2. Use a HART handheld communicator to perform a

Loop Test function at 20 mA, or place a Gas Test

Cell or an Optical Test Film into the detector light

beam (refer to Gas Test Cell Method and Optical

Test Film Method sections above). Verify correct

output at the control device.

3. Remove the gas test cell or optical test film, if

necessary, and re-activate alarm response at the

control device.

Relay Output Models
The following should be performed to verify correct

alarm and trouble relay activation.

Fault Relay
1. Inhibit fault response at the control device.
2. Completely block the light beam with a solid object

such as a piece of cardboard until a beam block

fault is generated. Verify correct change of state at

the control device.

3. Re-activate fault response at the control device.

Alarm Relays
1. Inhibit alarm response at the control device.
2. Temporarily configure the High Alarm relay to 1

LFL-meter; then place a High Range gas test cell or

optical test film into the light beam (refer to Gas Test

Cell Method and Optical Test Film Method sections

above). Verify correct change of state at the control

device.

3. Remove the gas test cell or optical test film to return

the high alarm relay to its original state. Return

configuration of the High Alarm relay to the original

value. Re-activate alarm response at the control

device.

FAULT/FAILURE ACTION PLAN
In the event that a Calibration does not result in

acceptable Gas Response Proof test, then the standard

Maintenance, Troubleshooting, and Device Repair and

Return procedures as listed in the OPECL instruction

manual must be followed. Any failure to successfully

complete the Gas Response Proof Test must be

recorded and documented in the SIS logbook and

reported to the manufacturer.

PRODUCT REPAIR
The OPECL transmitter and receiver electronics

modules can be replaced in the field as listed in the

Replacing OPECL Transmitter/Receiver Electronics

Module section of the OPECL instruction manual. Any

internal device repairs other than electronics module

replacement must be conducted at the factory. No

firmware changes are permitted or authorized. All

failures detected by the internal diagnostics or by the

Proof Test must be reported to the manufacturer.

OPERATING, ENVIRONMENTAL, AND
PERFORMANCE SPECIFICATIONS
The operating temperature range for the Safety Certified

OPECL is –40°C to +60°C. The Safety-Certified

OPECL product versions fully comply with, and must

be operated in accordance with, the other functional,

environmental (including EMC considerations), and

performance specifications provided in the OPECL

instruction manual. A 24 hour mean time to repair

should be assumed for safety availability calculations.

SPARE PARTS
Refer to “Spare Parts” in the OPECL instruction manual.

Safety Certification is based on a sufficient number of

spares to achieve a 24 hour mean time to repair.