Is used, wire the manual, Test – Det-Tronics U7652B, C Unitized UV/IR Flame Detector User Manual

Page 11

Advertising
background image

Note that non-isolated operation requires installation
of a jumper wire between pins CON 1-1 and CON 1-9
(current sourcing) or between pins CON 2-2 and CON
2-9 (current sinking) on the detector terminal block.

Figure 13 — U7652C Detector with 4 to 20 ma

Output Wired for Isolated Current
Sinking Output

Note that isolated operation requires the use of a sep-
arate power supply.

1.

Mount the detector and mounting bracket assem-
bly. The mounting surface should be free of
excessive heat and vibration.

2.

Remove the junction box cover.

3.

Route the field wiring through the detector conduit
entry.

4.

Connect the leadwires to the appropriate screw
terminals on the terminal blocks inside the junc-
tion box. Connect the shield to earth ground at
the power source. Do not ground the shield at
the detector/controller housing (unless required
by local codes).

5.

If manual

oi

is used, wire the manual

oi

test

switches (optional) by connecting a normally
open switch, capable of switching 1 ma at 5 vdc
and with contact resistance no more than 25
ohms, between the negative (–) side of the dc
power source and the terminal marked “

oi

” on

the detector terminal block. Each detector should
have its own

oi

test switch to allow individual

detector testing.

6.

Check all field wiring to be sure that the proper
connections have been made, and also double
check the jumper plugs for correct position. If
conduit is used, pour the conduit seals and allow
them to dry.

7.

Re-install the junction box cover, ensuring that the
9-pin “D” connectors are properly mated between
the cover and the circuit board inside the enclo-
sure. The six screws must be tight to ensure a
metal-to-metal fit for explosion-proof and water-
tight integrity of the junction box.

8.

Inspect and clean (if necessary) the detector
viewing windows and

oi

rings by following the

instructions in the “Maintenance” section.

9.

Re-install the

oi

rings. The opening should be

pointed down to minimize the accumulation of
moisture or contaminants behind the ring. Verify
that the

oi

test lamp is at the top or side of each

sensor.

10. If the detector is so equipped, install the air

shields on each sensor housing, then connect the
air supply line to the air shields.

DETECTOR PROGRAMMING

The U7652 provides three standard field pro-
grammable options:

— 0.5 or 3 second response time
— Latching or non-latching alarm output
— Automatic or manually activated

oi

test.

9

95-8385

D1441

+

24 VDC

LOAD

875 MAX

AT 24 VDC INPUT

+

4 TO 20 MA

MINIMUM OF 6.5 VDC REQUIRED
BETWEEN CON 1–9 AND CON 2–9

9

8

7

6

5

4

3

2

1

9

8

7

6

5

4

3

2

1

CON 1

CON 2

+

4 TO 20 MA

FIRE RELAY

FAULT RELAY

Figure 12—U7652C Detector with 4 to 20 ma Output Wired for

Non-Isolated Current Sourcing Output

MINIMUM OF 6.5 VDC REQUIRED
BETWEEN CON 1–9 AND CON 2–9

D1442

875 MAX

AT 24 VDC INPUT

+

24 VDC

+

24 VDC

+

4 TO 20 MA

9

8

7

6

5

4

3

2

1

9

8

7

6

5

4

3

2

1

CON 1

CON 2

+

4 TO 20 MA

FIRE RELAY

FAULT RELAY

Figure 13—U7652C Detector with 4 to 20 ma Output Wired for

Isolated Current Sinking Output

Advertising