MOUNTING AND WIRING PROCEDURE

The following procedure should be used for mounting and
wiring the detector. Refer to the following illustrations:

Figure 4 —

Detector Junction Box with Cover
Removed (Terminal Blocks,
Programming Jumpers, Motherboard
Assembly)

Figure 5 —

Detector Dimensions

Figure 6 —

Swivel Mounting Bracket Dimensions

Figure 7 —

U7652B Wiring Terminal
Configuration

PROVIDE ENOUGH CABLE
FOR ADJUSTMENT OF SWIVEL

CONDUIT SEAL

A1478

Figure 3—Vertical Mounting

B1437

TERMINAL BLOCK

AUXILIARY RELAY OPERATION (W4)

LATCH/NON-LATCH (W1)

ALARM RESPONSE (W3)
oi TEST (W2)

CONNECTOR

SCREWS (3)

MOTHERBOARD ASSEMBLY

Figure 4—Detector Junction Box with Cover Removed (Terminal Blocks, Programming Jumpers, Motherboard Assembly)

6

oi

RING

OPENING
DOWN

CONDUIT SEAL REQUIRED
WITHIN 18 INCHES OF
DETECTOR, WHICH MUST
BE ORIENTED WITH
CONDUIT ENTRY AT
BOTTOM OR SIDE TO
ELIMINATE DRAINAGE
INTO JUNCTION BOX.

*

oi

TEST LAMPS AT TOP OR SIDE

LED (2)

oi

TEST LAMP

*oi

TEST LAMP

(2)

LED (2)

IR SENSOR

HOUSING

UV SENSOR

HOUSING

C1327

Figure 2—U7652 Front View