Det-Tronics U7652B, C Unitized UV/IR Flame Detector User Manual

Page 4

Advertising
background image

oi

FEATURE

Both sensors are equipped with the Optical Integrity
(

oi

) test feature to assure proper operation of the

detector by checking the cleanliness of the optical
surfaces, sensitivity of the sensors, and proper func-
tioning of the electronic circuitry. No testing with an
external test lamp is required. The detector automati-
cally performs the same test that a maintenance per-
son with a test lamp would perform — once every
minute, 60 times per hour. A successful automatic

oi

test does not produce an alarm condition.

The U7652 can be programmed (using a jumper
plug) for automatic and/or manually initiated

oi

test-

ing. Use of automatic

oi

is highly recommended.

Automatic

oi

With automatic

oi

selected, the

oi

test is automatical-

ly performed on each sensor once every minute. If a
fault is detected, the normally energized Fault relay is
de-energized and the LEDs on the faulty sensor stop
blinking. When automatic

oi

is selected, the detector

can also be tested using the manual

oi

test.

Manual

oi

The detector also incorporates a manual

oi

feature

that provides the same test as the automatic

oi

, and

in addition actuates the Alarm relay to verify output
operation. The manual

oi

feature is available in all

models and can be performed at any time. This test
requires bypass of all extinguishing devices to
avoid release resulting from a successful test.

RELAYS AND OUTPUTS

All U7652 Models

All U7652 Models are furnished with two standard
output relays that are rated for 5 amperes (resistive)
at 30 vdc.

Fire relay has SPDT (normally open/normally closed)
contacts:

— Normally de-energized (no fire).
— Energizes upon detection of fire.
— Field programmable for either latching or non-

latching operation.

Fault relay has SPST (normally open) contacts:

— Normally energized (no fault).
— De-energizes when fault is detected.
— Non-latching operation (automatically resets when

fault is corrected).

U7652C Model

The U7652C is furnished with either an auxiliary relay
or a 4 to 20 ma output in addition to the standard out-
puts. The U7652C with auxiliary relay requires the
presence of radiation at only one sensor for relay
actuation-rated for 1 ampere at 30 vdc. (Not recom-
mended for uncontrolled locations.)

Auxiliary relay has SPST (normally open) contacts.

— Field selectable for actuation when “UV radiation

only” or “any UV or IR radiation” is detected.
(Factory-shipped with the field selectable jumper
plug in the “UV only” position.)

— Normally de-energized (selected radiation not

detected).

— Energizes upon detection of selected radiation.

— Non-latching when responding to UV only or IR

only condition.

— Latches in response to UV and IR radiation at

background levels (fire threshold not exceeded).

Table 1—Detector Status Chart

2

Status

UV LEDs

IR LEDs

Fire Relay

Fault Relay

Normal

Blinking

Blinking

De-energized

Energized

UV Fault

Off

Blinking

De-energized

De-energized

IR Fault

Blinking

Off

De-energized

De-energized

General Fault

Off

Off

De-energized

De-energized

Background UV

On

Off*

De-energized

Energized

Background IR

Off*

On

De-energized

Energized

Fire

On

On

Energized

Energized

Manual

oi

Test

On

On

Energized

Energized

During normal operation when automatic

oi

is selected, LEDs blink once

every 5 seconds. During normal operation when manual

oi

is selected, UV

and IR sides blink alternately every 5 seconds.

*Some earlier models will blink under these conditions.