Det-Tronics U7652B, C Unitized UV/IR Flame Detector User Manual

Page 19

Advertising
background image

SPECTRAL SENSITIVITY RANGE—
UV: 0.185 to 0.245 micron.
IR:

4.45 microns.

Figure 19 illustrates the spectral response range of
the UV and IR sensors.

CONE OF VISION—
The detector has a nominal 90 degree cone of vision
with the highest sensitivity along its central axis. See
Figure 20.

SENSITIVITY—
The U7652 detects a 1 foot by 1 foot gasoline fire at
50 feet, a 2 foot by 2 foot JP4, 5, or 8 fire at 100 feet,
and a 3 foot by 3 foot JP4, 5, or 8 fire at 150 feet.

RESPONSE TIME—
Response time is a function of fuel, fire size, distance
and orientation of the fire. The detector is field pro-
grammable (using a jumper plug) for a 0.5 or 3 sec-
ond response time when exposed to a saturating fire
signal.

RELAY CONTACT RATING—
One Fire and one Fault relay, each rated 5 amperes
(resistive) at 30 vdc. The Auxiliary relay in the
U7652C is rated 1 ampere at 30 vdc. The Fire and
Auxiliary relays are field programmable for latching or
non-latching operation. In latching operation the relay
is reset by removing operating power for 0.1 second.

ENCLOSURE MATERIAL—
Copper-free aluminum (red) or 316 stainless steel,
with stainless steel mounting bracket.

TEMPERATURE RATING—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage:

–40°F to +185°F (–40°C to +85°C).

HUMIDITY RANGE—
0 to 95% RH. Can withstand 100% condensing
humidity for short periods of time.

CERTIFICATIONS—
FMR:

See Appendix A for details.

CSA:

Class I, Division 1, Groups B, C and D;
Class I, Division 2, Groups A, B, C and D
(T4A).
Class II/III, Division 1, Groups E, F, and
G; Class II/III, Division 2, Groups F and G
(T4A).
Enclosure Type 4X

ULC:

Explosion-proof for Class I, Division 1,
Groups C and D.
Dust ignition-proof for Class II, Division 1,
Groups E, F, and G.

17

95-8385

5.0

4.0

3.0

2.0

1.5

1.0

0.9

0.8

0.7

0.6

0.5

0.4

0.3

0.2

0.1

ATMOSPHERIC

TRANSMISSION

WAVELENGTH (MICRONS)

SOLAR

RADIATION

REACHING

THE EARTH

INFRARED

SENSOR

RESPONSE

VISIBLE

INFRARED

ULTRAVIOLET

SENSOR

RESPONSE

ULTRAVIOLET

100

75

50

25

0

A1070

Figure 19—UV and IR Spectral Response Range

0°

15°

30°

45°

15°

30°

45°

VIEWING ANGLE

A1288

100

90

80

70

60

50

40

30

20

10

DETECTION

DISTANCE

(PERCENT)

100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A

GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF

INCIDENCE DECREASES.

Figure 20—Detector Cone of Vision (Gasoline)

Advertising