Det-Tronics W867A, B 3001, 3002, 3003 UV/IR Explosion Proof Test Lamp User Manual

Instructions ultraviolet/infrared test lamp w867

Advertising
background image

APPLICATION

The Det-Tronics W867 Ultraviolet/Infrared (UV/IR)
Test Lamp is a portable, battery operated source of
ultraviolet and infrared radiation that can be used for
periodic inspection of UV, single frequency IR and
UV/IR flame detection systems. It produces UV and
IR radiation to verify response of the flame detection
system without the need for an open flame, and is
suitable for use in hazardous (classified) areas. (Note:
Det-Tronics Dual Frequency IR detectors require the
model W868 Dual Frequency IR Test Lamp for testing.)

SPECIFICATIONS

ENCLOSURE—

Cast aluminum.

CERTIFICATION—

Class I, Division 1, Groups C and D;

Class II, Division 1, Groups E, F and G.
For storage and use in dry or damp
locations only.

ELECTRICAL RATINGS—

Battery Charger Input Voltage:

120 volts ac, 60 Hz

220

volts

ac,

50

Hz

(optional).

TEMPERATURE RANGE—

Operating:

+5°F to +122°F (–15°C to +50°C).

Charge:

+32°F to +104°F (0°C to +40°C).

Storage:

+5°F to +104°F (–15°C to +40°C).

OPERATING TIME—

Approximately 15 minutes continuous between
recharges. This will vary with the ambient temperature.

OUTPUT—

Broadband emissions in both UV and IR spectra.

APPROXIMATE OPERATING RANGE—

UV detector (25 cps sensitivity setting):

>50 feet (15 meters).

IR detector (40 cps sensitivity setting):

5 feet (1.5 meters).

UV/IR detector (16 cps sensitivity setting):

5 feet (1.5 meters).

DIMENSIONS—

See Figure 1.

WEIGHT (APPROXIMATE)—

14 pounds (6.2 kg).

INSTRUCTIONS

Ultraviolet/Infrared Test Lamp

W867

F M

APPROVED

5.1

©

Detector Electronics Corporation 2007

9/07 95-8309

Advertising