3

95-8309

5.1

SYSTEM CHECKOUT

A system checkout should be performed after
installation is complete. A periodic maintenance
checkout (with minimum frequency of once every six
months) should be scheduled to ensure that the system
is in proper operating condition. Depending on the
degree of hazard and the amount of contaminants in
the atmosphere, the checkout can be scheduled more
often. Note that oil films will significantly reduce the
transmission of ultraviolet radiation through the detector
windows.

For specific system checkout instructions, see the
“Checkout Procedure” section of the instruction manual
for the flame detection system being used.

The W867 Test Lamp is a safe, portable UV/IR source
for external testing and verification of the response
of Det-Tronics UV, single frequency IR, and UV/IR
detectors. It is suitable for use in hazardous (classified)
areas, but is not a substitute for an actual open flame
test.

SERVICE PROCEDURES

BATTERY MAINTENANCE

A battery charge level indicating LED and the charger
cable connection for recharging the battery are located
beneath a removable windowed plug in front of the
ON pushbutton switch. See Figure 2. To maintain the
explosion-proof rating of the W867, the plug must be
installed whenever the battery is not being charged.
To determine the battery charge level, press the ON
pushbutton and observe the Indicating LED. When the
battery is fully charged, the red Indicating LED (viewed
through the window) is off. When the battery reaches
a marginal level, the Indicating LED will flash on and
off. The battery should be recharged at this time. If
the Indicating LED is on continuously, the battery is at a
very low level and the test lamp should not be operated
until the battery has been recharged.

WARNING

The life of the battery is significantly reduced
if it is operated when the red LED is on
continuously.

RECHARGING

A 12 volt dc, 0.3 ampere battery charger is provided
to supply dc voltage from an ac outlet for recharging
the W867 battery. Battery chargers are available to
operate on either 120 vac 60 Hz or 220 vac 50 Hz
(optional). This plug-in battery charger contains a
Power On LED to indicate when the charger is plugged
in and a Fast Charge LED to indicate when the battery
is being charged.

WARNING

Do not operate the W867 Test Lamp when the
battery is charging.

Do not recharge the battery in a hazardous area.

To recharge the battery, first remove the windowed plug
to gain access to the recharge connection. Plug the
charger cable plug into the battery. Plug the battery
charger into the appropriate ac outlet. The Power On
and Fast Charge LEDs on the battery charger should
be on. When the battery is fully charged, the Fast
Charge LED will go out. This should take from 12 to 14
hours from a discharged state.

To return the W867 Test Lamp to service, unplug the
battery charger from the ac outlet. Disconnect the
charger cable from the battery. Replace the windowed
plug. Press the ON pushbutton and observe the
indicating LED on the battery. The indicating LED
should be off, which shows that the battery is fully
charged and ready to operate.