Operation – Det-Tronics W867A, B 3001, 3002, 3003 UV/IR Explosion Proof Test Lamp User Manual

Page 2

Advertising
background image

2

95-8309

5.1

WARNING

Exposure to ultraviolet radiation from the
W867 Test Lamp can be damaging to the
eyes. Do not look directly into the window of
the test lamp when it is on.

OPERATION

To operate the W867 Test Lamp, push the “ON”
button (see Figure 2) and aim the test lamp at the
detector. The UV and IR emitting lamp inside the
W867 will flash on and off at a rate of approximately
2 times per second. This flashing operation satisfies
the “flicker” circuit in the IR detector. Response of
the detection system will depend upon the distance
between the W867 and the detector, and upon the
sensitivity programmed into the detection system. It
may be necessary to decrease the distance between
the detector and the test lamp in order to obtain a
response.

Do not operate the test lamp longer than is necessary
to actuate the detector. Each detector can be checked
with less than 30 seconds of operating time. It is
important to avoid discharging the battery to the point
where the battery charge level Indicating LED (see
Figure 2) is on steady. Refer to the Battery Maintenance
section of these instructions for further information.

CAUTION

Do not remove the shock insulators from the
lens cap or battery storage compartment.

A1713

4.25

(10.8)

7.38

(18.7)

10.38 (26.4)

7.00

(17.8)

10.625 (27.0)

3.75

(9.5)

TOP VIEW

S

IDE VIEW

Figure 1—W867 Test Lamp Dimensions in inches (cm)

A1714

WINDOWED PLUG

ON PU

S

HBUTTON

HANDLE

INDICATING LED

CHARGER CABLE CONNECTION

Figure 2—Top View of W867 Test Lamp