INSTALLATION CHECKLIST

The following checklist is provided as a means of
double checking the system to be sure that all phases
of system installation are complete and have been
performed correctly.

1. OPECL detector is installed as described in the

OPECL manual (95-8556).

IMPORTANT

To ensure proper operation, the OPECL must
be configured for PIR9400 Analog Fault Code.
Refer to the HART section in the OPECL manual
(95-8556) for more information.

2. OPECL housing covers are tightly installed.

3. All cable shields are properly grounded.

4. Conduit seals have been installed at all junction box

entries (if conduit is being used).

5. OPECL to controller wiring is correct.

6. Power wiring to OPECL and the controller is installed

and power source is operational.

7. External loads are properly connected to the

controller.

8. Controller is programmed as desired. Record this

information for future reference.

9. Controller is properly installed in the mounting

enclosure.

10. Proper ventilation is provided to prevent over-

heating of the controller.

Proceed to Startup Procedure, Setpoint Adjustment,
and Calibration.

STARTUP PROCEDURE

1. Output loads that are normally actuated by the

gas detection system should be secured (remove
power from all output devices) to prevent undesired
activation.

2. Check all external wiring for proper connection.

3. Before installing the controller in the mounting rack,

inspect it to verify that it has not been physically
damaged in shipment. Check the jumper plugs
and rocker switches on the controller for proper
programming, then slide the controller fully into the
mounting enclosure.

4. Apply power to the system.

NOTE

The controller has a power-up delay before
beginning normal operation after power is applied
to the system. During this time the outputs are
inhibited, the FAULT LED is illuminated, and
the current output indicates a fault condition.
This delay allows time for the OPECL output to
stabilize before beginning normal operation.

5. Put the controller in the Setpoint Display mode to

determine the present alarm setpoints. If changes
are required, perform the Setpoint Adjustment
procedure.

6. Perform the calibration procedure. This involves

zero calibrating the OPECL using the procedure
described in the OPECL manual, then calibrating
the controller using the procedure described in the
“Calibration” section of this manual.

7. Check the 4 to 20 mA current loop for proper

calibration and adjust as required.

8. After calibration is completed, restore the system

output loads to ready condition.