1.1

95-8572

5

MoDel PIrtB terMInatIon Box
The Model PIRTB Termination Box allows the operator
to initiate calibration of the OPECL detector from a
remote location. The PIRTB provides a magnetic reed
switch for initiating calibration and an LED to provide
calibration feedback. Refer to Figure 7 for an illustration
of an R8471J Controller wired to an OPECL IR gas
detector using a Model PIRTB termination box. Refer
to Figure 8 for location of the magnetic switch and LED
within the PIRTB enclosure.

100K

oPen collector oUtPUt

1n4004

tYPIcal

+32 vDc MaxIMUM

C1289

Figure 6—Open Collector Output with Inductive Load

and Transient Suppression Device

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

SP.

CAL

SIG

RET

+ 24

CAL

SIG

RET

+ 24

+

24 VDC

POWER SUPPLY

NOTES:

1.

REED SWITCH, LED, AND ALL INTERNAL CONNECTIONS ARE PROVIDED ON

THE PIRTB CONNECTOR BOARD.

2.

CONDUCT OPECL CALIBRATION PROCEDURE BEFORE

R8471J CONTROLLER CALIBRATION.

3.

OPECL CALIBRATION INITIATION WILL CAUSE R8471J FAULT

CONDITION UNTIL OPECL CALIBRATION PROCEDURE IS COMPLETED.

4.

CABLE SHIELD WIRE IS TO BE CUT BACK AND TAPED OFF WITHIN

PIRTB JUNCTION BOX.

5.

CABLE SHIELD WIRE IS TO BE CONNECTED TO TERMINAL NO. 3 AT R8471J

BACKPLATE, WHICH IS THE CONTROLLER EARTH GROUND CONNECTION.

MAGNETIC REED SWITCH

FOR OPECL

CALIBRATION COMMAND

A2414

–24 VDC

+24 VDC

– 4-20 MA

CALIBRATE

1

2

3

4

5

6

7

8

9

10

11

12

13

MODEL OPECL

GAS DETECTOR

R8471J

CONTROLLER

+ 4-20 MA

–24 VDC

+24 VDC

2

1

NOTES:

1 INTERNAL JUMPER REQUIRED

FOR NON-ISOLATED CURRENT

OUTPUT (SINGLE POWER

SUPPLY).

2 250 OHM RESISTOR REQUIRED.

Figure 7—R8471J Controller Wired to an OPECL IR Detector with a Model PIRTB Termination Box