Table 2—Troubleshooting Guide

Indication at controller

Possible cause

No faceplate indicators

illuminated.

Input power failure. Check wiring to external power source.

FAULT LED on, digital display

blank.

Power-up time delay (up to 5 minutes). If condition continues after 5

minutes, repeat power-up. If problem continues, replace controller.

F91 to F98 Status

Initialization failure. Repeat power-up. If successful, re-program and

re-calibrate. If not, replace controller.

F92 Status

OPECL problem (during startup) - current is over 5 ma or below 0.5 mA.

F94 Status

RAM failure. Repeat power-up. If not successful, return to factory for

repair.

F96 Status

Input power upon startup out of spec (should be 18 to 2 volts). Check

operation of power source and power wiring. Correct problem and repeat

power-up.

F97 Status

Controller type invalid. Error in data from RAM. Repeat power-up. If not

successful, return to factory for repair.

F70 Status

External reset activated for over 15 seconds. Check external switch and

wiring.

F60 Status

Input power out of tolerance. Check operation of power source and power

wiring.

F50 Status

Internal power supply problem. Replace controller.

F40 Status

OPECL output (after startup) is over 5 mA or below 0.5 mA. Check

OPECL wiring and calibration.

F41 Status

OPECL has blocked optics. Refer to OPECL manual.

F42 Status

OPECL calibration line fault.

F0 Status

Negative zero drift. Check OPECL alignment and calibration.

CAL

OPECL in calibrate mode, doing Zero calibration.

CC

OPECL in calibrate mode, successful calibration completed.